Emerson KC3030X1-BK2 S-Series Four-Port Fieldbus H1 Plus Card
Four isolated FOUNDATION Fieldbus H1 ports for a DeltaV S-series I/O carrier
Product Presentation
Four FOUNDATION Fieldbus H1 segments meet the DeltaV controller through Emerson KC3030X1-BK2. Each port operates at 31.25 kbit/s and is isolated from the other ports and from the system, keeping the segment interfaces electrically separated inside one S-series card.
Local-bus demand for KC3030X1-BK2 is 200 mA at the nominal 12 VDC carrier supply, with 3.9 W heat dissipation in either simplex or redundant use. Fieldbus power is specified separately at 9 to 32 VDC and 12 mA per port.
Installation of KC3030X1-BK2 is limited to an assigned position on an S-series I/O carrier with an S-series controller. The card itself does not provide generic field-circuit power; its four H1 interfaces work with the selected fieldbus termination and power architecture.
Engineering Specifications
| Technical Item | KC3030X1-BK2 |
|---|---|
| Brand | Emerson |
| Product Type | S-Series Fieldbus H1 four-port Plus card |
| Brand Country | United States |
| Number of Ports | 4 |
| Port Protocol and Rate | FOUNDATION Fieldbus H1 at 31.25 kbit/s |
| LocalBus Current | 200 mA typical at nominal 12 VDC |
| Field Circuit Power | None provided by the card |
| Fieldbus Power | 9 to 32 VDC, 12 mA per port |
| Heat Dissipation | 3.9 W in simplex or redundant use |
| Port Isolation | Each port isolated from the system and from every other port |
| Factory Isolation Test | 1,000 VDC |
| Mounting | Assigned slot of an S-Series I/O carrier |
| Controller Requirement | S-Series controller |
| Operating Arrangement | Simplex or redundant card configuration |
Four Isolated H1 Ports
Each H1 port has its own isolated path to the fieldbus segment.
KC3030X1-BK2 presents four FOUNDATION Fieldbus H1 ports at 31.25 kbit/s. Isolation between ports and between each port and the system keeps a segment electrical condition from becoming a shared conductive path through the card.
Port-level separation
The four interfaces on KC3030X1-BK2 are individually isolated and factory-tested to 1,000 VDC.
Segment assignment
Every H1 port on KC3030X1-BK2 is configured as its own fieldbus segment rather than combined as one multi-drop terminal bank.
Fieldbus Power and Carrier Placement
KC3030X1-BK2 uses 200 mA typical from the 12 VDC local bus for card operation.
Each port of KC3030X1-BK2 is specified for 9 to 32 VDC fieldbus power at 12 mA, separate from generic field-circuit power.
The installed position of KC3030X1-BK2 is an assigned S-series I/O-carrier slot under an S-series controller.
Support Questions
How many independent segments can KC3030X1-BK2 interface?
KC3030X1-BK2 provides four FOUNDATION Fieldbus H1 ports. Each port is treated as an isolated segment interface rather than four connectors on one shared channel.
What does KC3030X1-BK2 supply to an H1 port?
The fieldbus-power specification of KC3030X1-BK2 is 9 to 32 VDC at 12 mA per port. The complete segment still needs the intended fieldbus power and termination architecture.
Why is the isolation figure important on KC3030X1-BK2?
Every port on KC3030X1-BK2 is isolated from the system and from the other ports, with a 1,000 VDC factory test. That boundary helps keep separate H1 segments from sharing a conductive fault path through the card.
Which controller family is required for KC3030X1-BK2?
KC3030X1-BK2 requires an S-series controller and mounts in an assigned S-series I/O-carrier slot. A similar DeltaV form factor in another series does not establish compatibility.
How much cabinet heat should be assigned to KC3030X1-BK2?
The documented dissipation of KC3030X1-BK2 is 3.9 W in both simplex and redundant arrangements. Cabinet thermal calculations should count each installed card.
Does KC3030X1-BK2 provide a general-purpose 24 V field circuit supply?
No generic field-circuit power is provided by KC3030X1-BK2. Its power entries distinguish local-bus card power from the fieldbus power associated with each H1 port.
Technical Documentation Desk
Moore Automation
https://www.mvme.cn/Moore Automation organizes available manuals, data sheets and product records around Emerson KC3030X1-BK2. Technical information is kept with the requested identity, and one assigned contact coordinates document questions across established automation product families.
More Model Options
| Control & Process | PLC & I/O | Monitoring & Network | Drives & Power |
|---|---|---|---|
| 01Allen-Bradley 1756-RM2 | 16GE IC600PM503 | 31Emerson VE4005S2B2 | 46Foxboro RH916TA |
| 02Emerson VE4003S2B1 | 17Horner HE800DIM410 | 32ABB CI854AK01 | 47ICS Triplex T8151C |
| 03ABB PM891K01 | 18Foxboro RH101SF | 33Yokogawa ATSS3S | 48Allen-Bradley 1756-A13 |
| 04Yokogawa AEA4D | 19ICS Triplex T8111C | 34Siemens 6ES7414-3FM07-0AB0 | 49Emerson VE4005S2B4 |
| 05Siemens 6ES7414-3EM07-0AB0 | 20Honeywell TC-201-02-15M0 | 35GE IC600PM542 | 50ABB CI856K01 |
| 06GE IC600PM502 | 21Allen-Bradley 1756-A4 | 36Horner HE800DQM406 | 51Yokogawa ATD5A |
| 07Horner HE800DIM310 | 22Emerson VE4035S2B1 | 37Foxboro FBM242 | 52Siemens 6ES7417-4HL04-0AB0 |
| 08Foxboro FBM228 | 23ABB CI853K01 | 38ICS Triplex T8310C | 53GE IC630CPU301 |
| 09ICS Triplex T8461C | 24Yokogawa ATSA3D | 39Allen-Bradley 1756-A10 | 54Horner HE800DIQ716 |
| 10Honeywell TC-203-02-10M5 | 25Siemens 6ES7417-4HT14-0AB0 | 40Emerson VE4005S2B3 | 55Foxboro FBM211 |
| 11Allen-Bradley 1756-RM2XT | 26GE IC600PM541 | 41ABB CI855K01 | 56ICS Triplex T8153C |
| 12Emerson VE4005S2B1 | 27Horner HE800DQM306 | 42Yokogawa ATSS3D | 57Allen-Bradley 1756-A17 |
| 13ABB CI851K01 | 28Foxboro P0922QS | 43Siemens 6ES7416-3FS07-0AB0 | 58Emerson VE4035S2B4 |
| 14Yokogawa ATSA3S | 29ICS Triplex T8403C | 44GE IC600YB801 | 59ABB CI857K01 |
| 15Siemens 6ES7416-3ES07-0AB0 | 30Allen-Bradley 1756-A7 | 45Horner HE800DIQ712 | 60Yokogawa ARM15A |









No related record found