Emerson KJ3225X1-BA2 RTD / Resistance Input Card
DeltaV resistance-input hardware with C3 terminal-block keying
Model Summary
Resistance measurement is the defined role of Emerson KJ3225X1-BA2, a DeltaV RTD / Resistance Input Card powered from the 12 VDC local bus. The card forms the controller-side measurement path for compatible resistance-based field circuits while remaining mechanically paired with its keyed terminal block.
Within the installed I/O assembly, the rotary key assigned to KJ3225X1-BA2 is position C3. That keying boundary keeps the card aligned with the intended terminal block after installation and separates it from neighboring DeltaV card types that may share the same carrier form.
Industrial environmental limits are part of the hardware identity of KJ3225X1-BA2: the card is rated from -40 to +70 °C, 5 to 95% non-condensing humidity and ISA-S71.04 Class G3 airborne contaminants. Its certified arrangement also carries Class I Division 2 and Zone 2 markings for the documented enclosure and system installation.
Technical Reference
| Technical Item | KJ3225X1-BA2 |
|---|---|
| Brand | Emerson |
| Product Type | RTD / Resistance Input Card |
| Brand Country | United States |
| Local Bus Power | 12 VDC at 160 mA |
| Ambient Temperature | -40 to +70 °C |
| Relative Humidity | 5 to 95%, non-condensing |
| Shock | 10 g half-sine wave for 11 ms |
| Vibration, Low Frequency | 1 mm peak-to-peak from 2 to 13.2 Hz |
| Vibration, High Frequency | 0.7 g from 13.2 to 150 Hz |
| Airborne Contaminants | ISA-S71.04-1985 Class G3 |
| Terminal Block Key | C3 |
| Hazardous-Area Marking | II 3G Ex ec IIC Gc; Class I Division 2; Zone 2 |
| Removal Boundary | Field and system power removed before insertion or removal |
| Calibration | Not required |
RTD Excitation and Resistance Paths
The card keeps sensor resistance and controller processing in one defined input path.
KJ3225X1-BA2 receives the resistance measurement through the keyed field termination and passes the converted value across the DeltaV local bus. The input function is fixed by the card identity rather than inferred from a neighboring module label.
Excitation boundary
The resistance circuit connected to KJ3225X1-BA2 remains tied to the card and matching terminal block, preserving the intended measurement path through the carrier.
No calibration routine
KJ3225X1-BA2 is documented without a field-calibration requirement and contains no user-serviceable internal parts.
Card-to-Terminal Keying
The C3 rotary position is the physical compatibility marker for KJ3225X1-BA2 and its intended terminal block.
Both field power and system power are removed before KJ3225X1-BA2 is connected, inserted or removed.
The marked component approvals for KJ3225X1-BA2 apply within the complete DeltaV Zone 2 installation and enclosure rules.
User Questions
Which terminal-block key belongs with KJ3225X1-BA2?
The documented rotary key position for KJ3225X1-BA2 is C3. Matching that position before installation prevents a mechanically similar but functionally different terminal block from being paired with the card.
Can KJ3225X1-BA2 be inserted while the DeltaV carrier remains energized?
KJ3225X1-BA2 is not an energized insertion or removal device. Field power and system power must both be removed before the card is connected or withdrawn.
What local-bus load must be reserved for KJ3225X1-BA2?
The local-bus requirement of KJ3225X1-BA2 is 12 VDC at 160 mA. The carrier power calculation should include that current for every installed card.
Does KJ3225X1-BA2 need a field calibration after installation?
No field-calibration adjustment is specified for KJ3225X1-BA2. A channel check should instead confirm the sensor circuit, terminal assignment and expected resistance value.
How should a humidity concern be judged for KJ3225X1-BA2?
KJ3225X1-BA2 is rated for 5 to 95% relative humidity only when the atmosphere is non-condensing. Visible moisture or condensation is therefore outside the stated environmental condition.
What does the G3 rating mean for KJ3225X1-BA2 installation planning?
The airborne-contaminant classification for KJ3225X1-BA2 is ISA-S71.04 Class G3. The complete cabinet still has to maintain the environmental and hazardous-area conditions assigned to the DeltaV installation.
Dedicated Account Coordination
Moore Automation
https://www.mvme.cn/Moore Automation assigns one account contact to keep the complete Emerson KJ3225X1-BA2 identity, requested quantity and destination in one controlled record. Prompt acknowledgement, clear follow-up and a consistent communication path keep technical and delivery details aligned from the first message onward.
Associated Products
| Control & Process | PLC & I/O | Monitoring & Network | Drives & Power |
|---|---|---|---|
| 01ABB PM5072-R-ETH | 16ABB PM5112-R-ETH | 31Allen-Bradley 1756-L61 | 46Emerson VE3051C0 |
| 02Allen-Bradley 1769-L16ER-BB1B | 17Allen-Bradley 1769-L18ERM-BB1B | 32Emerson VE3011 | 47Honeywell CC-PAIX01 |
| 03Emerson VE3006 | 18Emerson VE3008 | 33Honeywell CC-TCNT04 | 48ABB TP830 |
| 04Honeywell CC-PCNT01 | 19Honeywell CC-PCNT03 | 34ABB SS823 | 49Yokogawa AAV142 |
| 05ABB SD831 | 20ABB SD833 | 35Yokogawa AAI141 | 50GE IC200MDL740 |
| 06Yokogawa A2FV50S | 21Yokogawa A2FV70S | 36GE IC200CPUE05 | 51ABB DI524 |
| 07GE IC695MDL740 | 22GE IC694MDL740 | 37ABB PM581-ETH | 52Allen-Bradley 1756-L64 |
| 08Bently Nevada 3301S2 | 23ABB PM5132-T-ETH | 38Allen-Bradley 1756-L62 | 53Emerson VE3051C1 |
| 09ABB PM5072-T-ETH | 24Allen-Bradley 1769-L30ER-NSE | 39Emerson VE3012 | 54Honeywell CC-PAOH01 |
| 10Allen-Bradley 1769-L18ER-BB1B | 25Emerson VE3009 | 40Honeywell CC-PAIH01 | 55ABB TP831 |
| 11Emerson VE3007 | 26Honeywell CC-TCNT03 | 41ABB SS832 | 56Yokogawa AAB141 |
| 12Honeywell CC-PCNT02 | 27ABB SD834 | 42Yokogawa AAV141 | 57GE IC200ALG264 |
| 13ABB SD832 | 28Yokogawa A2FV70D | 43GE IC200MDL650 | 58ABB DI525 |
| 14Yokogawa A2FV50D | 29GE IC694ALG223 | 44ABB PM582-ETH | 59Allen-Bradley 1756-L65 |
| 15GE IC694MDL645 | 30ABB PM571-ETH | 45Allen-Bradley 1756-L63 | 60Emerson VE3051C2 |





No related record found