Local write
The host writes a configured location in the local reflective-memory window. A network offset can place nodes into aligned memory groups.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC695RMX228-ACAB Redundancy Memory Xchange Module |
| Item NO. | 2944609 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-24 |
GE Fanuc · PACSystems RX3i
ACAB hardware · 128 MB SDRAM · 2.12 Gbaud fiber ring
GE Fanuc IC695RMX228-ACAB is a PACSystems RX3i Redundancy Memory Xchange module with single-mode fiber interfaces. It mirrors selected memory across a deterministic fiber network and can provide the dedicated two-node link between primary and secondary RX3i redundancy systems.
Data written into IC695RMX228-ACAB reflective memory is transferred around the daisy-chained fiber loop so the corresponding memory location is updated at each node. The module contains 128 MB SDRAM, uses a 2.12 Gbaud optical network and connects through LC single-mode interfaces for links up to 10 km.
When IC695RMX228-ACAB serves as a CPU-redundancy link, the path must remain a two-node ring with one RMX in each controller and two crossed fiber connections. That redundancy link cannot simultaneously be used as a general reflective-memory network, and mixed single-mode/multimode paths require a compatible hub.
IC695RMX228-ACAB distributes a memory write through hardware-managed optical transfers rather than message-by-message application logic.
The host writes a configured location in the local reflective-memory window. A network offset can place nodes into aligned memory groups.
The module packetizes changed data and sends it through the 2.12 Gbaud fiber loop. Each downstream node repeats the transfer.
The matching location is updated at the receiving nodes, allowing controllers or computers to read a synchronized memory image.
The physical ring used by IC695RMX228-ACAB determines whether the module acts as a general memory node or a redundancy link.
Each transmitter connects to the receiver of the next node. A reversed or open pair prevents the loop from completing.
A hot-standby link uses exactly two RMX modules and two fibers. No hub or additional reflective-memory node is inserted in that ring.
IC695RMX228-ACAB uses single-mode optics. Direct connection to a multimode card is not permitted; mixed networks require the specified conversion hub.
No. IC695RMX228-ACAB is single-mode; a compatible reflective-memory hub is required when single-mode and multimode nodes share a general network.
Use IC695RMX228-ACAB link indicators and loop diagnostics to confirm optical continuity, then compare node IDs, offsets and mapped memory ranges.
Record the IC695RMX228-ACAB suffix, firmware, node ID, memory offset, redundancy role, fiber routing, port LEDs and host configuration.
IC695RMX228-ACAB identifies -ACxx hardware with firmware 2.01 and the March 2016 power-cycle correction; verify the complete label before interchange.
For IC695RMX228-ACAB, verify LC end-face cleanliness, transmit-to-receive polarity, bend radius and continuity around the complete ring.
In redundancy mode IC695RMX228-ACAB uses a dedicated two-node path for controller synchronization; adding other nodes changes that controlled topology.
Moore Automation supports industrial automation enquiries by organizing model verification, available technical documents, quotation details and shipment information into one record. Each step is tied to the full requested catalog string rather than a shortened family name.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.