Input bank A
Inputs 1-8 share the first common. Positive-logic wiring sources current into the input; negative-logic wiring reverses the path through the assigned common.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC200MDD842F 16-Input / 16-Output Mixed Module |
| Item NO. | 2944607 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-24 |
GE Fanuc · VersaMax
F revision · ESCP protected outputs · dual input groups
GE Fanuc IC200MDD842F is a VersaMax mixed discrete I/O module combining sixteen 24 VDC inputs with sixteen 24 VDC sourcing outputs. The CPU or NIU reads one 16-bit input block and writes one 16-bit output block through a single carrier-mounted module.
On IC200MDD842F, the inputs are divided into two groups of eight with separate common terminals, while all sixteen outputs form one field-power group. The input groups can be wired for positive or negative logic; the output group switches the positive side of the external DC supply to the loads.
Each IC200MDD842F output includes electronic overcurrent and short-circuit protection. Green point LEDs indicate commanded states, amber point LEDs identify overloads, and configurable input filtering changes the total response between 0.5 ms, 1.5 ms and 7.5 ms.
IC200MDD842F places two different signal directions on one carrier while keeping their commons and power paths identifiable.
Inputs 1-8 share the first common. Positive-logic wiring sources current into the input; negative-logic wiring reverses the path through the assigned common.
Inputs 9-16 use the second common, so a problem on one common can affect eight inputs without necessarily changing the other group.
Outputs 1-16 share DC+ and DC-. Each channel switches the positive field supply to its load, while the return remains on the common DC path.
The output protection in IC200MDD842F reacts per point while reporting a summarized module condition to the controller.
An overloaded or shorted output illuminates its amber indicator. The green output LED still follows the commanded state and does not prove load current is flowing.
A weak external supply can collapse during a short-circuit event and disturb multiple points. Supply capacity and wiring resistance therefore affect recovery behavior.
After the overload is removed, the protected output resumes normal operation. The controller-level diagnostic and point LED can be used together to locate the affected circuit.
Use IC200MDD842F 0 ms filtering for the fastest 0.5 ms response, 1.0 ms for the 1.5 ms default response, or 7.0 ms where bounce/noise requires a 7.5 ms total response.
An amber IC200MDD842F LED identifies an overload on that output point; compare it with the commanded green state and the external supply voltage.
Record the IC200MDD842F revision, input logic polarity, two common assignments, output supply, filter setting and any amber overload indications.
For IC200MDD842F, inspect the common serving that eight-point group and confirm whether the field wiring uses positive or negative logic.
For IC200MDD842F, an external supply unable to sustain short-circuit energy can dip below the operating range and disturb more than the protected point.
IC200MDD842F output LEDs follow commanded state and depend on field power but not load continuity, so inspect the load path and return separately.
Moore Automation handles enquiries across established control families including GE Fanuc VersaMax and PACSystems, ABB AC500 and AC800M, Siemens SIMATIC and SINAMICS, and Bently Nevada monitoring components. The brand and full catalog string remain paired throughout the request.