IQS453 204-453-000-011 / IQS453 204-453-000-021 share the same long-range conversion behaviour, while their five-metre and ten-metre calibrations keep each conditioner aligned with its assigned TQ4x3 chain.
-
01
Twelve-millimetre measurement span
Both IQS453 204-453-000-011 / IQS453 204-453-000-021 condition the response of a TQ4x3 probe across a nominal 12 mm range. The 1.33 mV/µm scale relates target displacement to the three-wire voltage delivered by the complete chain.
-
02
Static and dynamic response
The DC component from IQS453 204-453-000-011 / IQS453 204-453-000-021 represents the steady probe-to-target gap. Response through 20 kHz carries changing displacement so one signal path serves position and vibration measurement.
-
03
Supply and load behaviour
Each IQS453 204-453-000-011 / IQS453 204-453-000-021 receives -20 to -32 VDC and normally draws 13 ±1 mA. The voltage output has 500 ohm impedance and short-circuit protection for the connection to the monitoring input.