Command
The controller writes a signed output value into the channel’s assigned I/O data.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC200ALG322G VersaMax Analog Output Module |
| Item NO. | 2945439 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-26 |
GE Fanuc · VersaMax
Four single-ended bipolar voltage outputs with a selectable power-up default for the field channels.
GE Fanuc IC200ALG322G is a four-channel VersaMax analog voltage output module. It receives four commanded values from the I/O bus and converts each value into a single-ended field voltage over the ±10.24 V range.
The output converter of IC200ALG322G uses 12-bit resolution, producing 5 mV increments and updating all channels within 0.3 ms. The field side requires an external 18–30 VDC supply, while the backplane provides logic power and the data path to the controller.
A module jumper determines whether IC200ALG322G holds the last commanded output or drives the channels to zero when the I/O connection is lost. Field power and OK indicators distinguish missing output power from a module or communication condition before individual channel wiring is examined.
| Technical Item | IC200ALG322G |
|---|---|
| Brand | GE Fanuc |
| Product Type | VersaMax four-channel analog voltage output module |
| Brand Country | United States |
| Output Channels | 4, single-ended |
| Output Range | −10.24 to +10.24 VDC |
| Resolution | 12 bit; 5 mV per count |
| Maximum Update Time | 0.3 ms for all channels |
| External Supply | 18–30 VDC |
| Backplane Current | 50 mA maximum from 5 VDC |
| Minimum Resistive Load | 5,000 ohms |
| Maximum Load Capacitance | 1.0 µF |
| Crosstalk | 70 dB |
| Loss-of-Communication Default | Hold last state or zero, jumper selected |
| Isolation | 250 VAC continuous field-to-logic; no channel-to-channel isolation |
Each command for IC200ALG322G passes through a shared module data path and a dedicated channel output circuit.
The controller writes a signed output value into the channel’s assigned I/O data.
The module relates that value to the bipolar ±10.24 V engineering span.
A 12-bit converter resolves the command into 5 mV output increments.
The channel circuit applies the voltage to the field load from the external DC supply.
Negative, zero and positive controller values occupy one bipolar data range. The converter maps that signed value around zero volts instead of treating the channel as a unipolar 0–10 V output.
A 5 mV increment is the smallest commanded step of the 12-bit conversion. It does not guarantee the connected load will settle to that value when supply, wiring or load impedance is outside the module boundary.
All four channels are refreshed within the documented module update period. Application scan and network timing are separate, so total command response includes more than the converter time alone.
A correct controller value cannot create the expected field voltage when the external 18–30 VDC source is absent. Compare the field-power LED with the commanded data before changing scaling.
The IC200ALG322G output return and cable arrangement determine how the converted signal reaches each load.
Run each voltage output with its assigned return to the receiving device.
Terminate cable shields according to the carrier and cabinet grounding plan without using them as signal returns.
Keep the receiving impedance above the specified minimum and capacitance within the output limit.
Set the hold-or-zero jumper to match the required state after I/O communication is lost.
Each load must be measured across its output and assigned return. Using a cabinet reference or another channel return can create a misleading voltage reading because the channels share a non-isolated module environment.
A cable shield controls coupled noise but is not the signal return. Its cabinet termination must follow the installation grounding plan so shield current does not flow through the analog measurement path.
The jumper applies one module-level choice: retain the last commanded values or drive outputs to zero. The selected behavior should be recorded with the process requirement before commissioning.
The four outputs are not isolated from one another. Field wiring must not assume independent galvanic boundaries between channels.
IC200ALG322G can have backplane logic power while the external 18–30 VDC field supply is missing. Check the field-power indication and measure the supply at the carrier before changing the controller value.
A hardware jumper on IC200ALG322G selects either hold-last-state or zero output when the I/O connection is lost. Record the jumper position before moving the module.
No. IC200ALG322G provides field-to-logic isolation but no channel-to-channel isolation. The returns and connected equipment must be planned with that shared electrical relationship in mind.
The receiving load on IC200ALG322G should be at least 5,000 ohms and no more than 1.0 µF capacitance. A heavier or highly capacitive load can prevent the command from settling correctly.
IC200ALG322G spans −10.24 to +10.24 V with 5 mV resolution. Apply the configured signed scaling and compare the resulting expected voltage with a measurement across the channel output and return.
The verified base function of IC200ALG322G remains the four-channel ±10.24 V output design. Keep the G revision in the supply record, but do not infer a different range without an exact revision notice.
https://www.mvme.cn/
Moore Automation keeps product questions tied to one clear enquiry record. Manufacturer, complete model, quantity and destination are reviewed together so later document or label checks refer to the same requested item.
Moore Automation · Send the complete manufacturer, model and destination details through the contact channel that suits your request.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found