Exchange data through the carrier
IC200BEM003-CA transfers cyclic input, output and diagnostic data through the communications carrier to the VersaMax CPU or supported PROFINET Scanner. The host determines the available memory resources.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE IC200BEM003-CA VersaMax PROFIBUS Master Module |
| Item NO. | 2940717 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-18 |
A VersaMax PROFIBUS-DP V1 master for CPU- and PNS-based I/O stations.
GE IC200BEM003-CA is a VersaMax PROFIBUS-DP V1 master module that installs on the IC200CHS006 communications carrier. It provides the controller-side master interface for cyclic input, output and diagnostic exchange between a VersaMax host and the PROFIBUS devices connected to the fieldbus segment.
GE IC200BEM003-CA operates with a compatible VersaMax CPU005, CPUE05 or supported PROFINET Scanner. Its PROFIBUS station address is configured in software, network operation covers data rates from 9.6 kbit/s to 12 Mbit/s, and one master can coordinate as many as 125 addressed slave stations.
Each slave connected to GE IC200BEM003-CA is defined by its GSD identity, installed module order and allocated I/O length. The module handles cyclic data together with Sync, Freeze and DP-V1 Read, Write and Alarm services, while its status indicators and diagnostic arrays separate host communication, bus activity and individual slave conditions.
| Specification | IC200BEM003-CA |
|---|---|
| Brand | GE |
| Product name | VersaMax PROFIBUS master module |
| Installation | VersaMax communications carrier IC200CHS006 |
| Network role | PROFIBUS-DP V1 master |
| Power consumption | 450 mA at 5 V DC |
| Station address | 0 to 125, software configurable |
| Default station address | 0 |
| Maximum slaves | 125 |
| Network data rate | 9.6 kbit/s to 12 Mbit/s |
| CPU data capacity | Up to 3584 bytes input and 3584 bytes output |
| PNS data capacity | Up to 1440 bytes input and 1440 bytes output |
| Per-slave data | Up to 244 bytes input and 244 bytes output |
| Device definition | Slave devices created from GSD files |
| Services | Sync, Freeze and DP-V1 Read/Write/Alarm |
| Isolation | 1500 V AC network-to-backplane minimum |
The module links a VersaMax host, one PROFIBUS segment and the configured slave database into a cyclic I/O system.
IC200BEM003-CA transfers cyclic input, output and diagnostic data through the communications carrier to the VersaMax CPU or supported PROFINET Scanner. The host determines the available memory resources.
A slave entry combines station address, GSD identity, installed module order and byte mapping. The master scans that stored structure and exposes mismatches as network diagnostics.
PROFIBUS timing is shared by every station on the segment. Data rate, cable length, repeater boundaries and slave response times together determine the completed scan cycle.
The diagnostic path distinguishes master state, segment health and individual slave configuration.
The front indicators distinguish module operation from active PROFIBUS exchange. A healthy host interface can therefore coexist with an offline fieldbus segment.
When several consecutive slaves disappear, the first missing address often marks the cable, connector or powered-device boundary. The two physical ends remain the only terminated points.
A single offline slave can report address, GSD identity, parameter or module-layout differences while the rest of the segment continues cyclic exchange.
Moore Automation coordinates PROFIBUS module enquiries with the surrounding carrier, cable, connector and slave-device requirements. The commercial record can keep the exact model, network accessories, destination and shipment details together for one complete request.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.