Feed the RX3i rails
IC695PSD140E converts the incoming DC source into the backplane voltages used by IC695 modules and the relay-output supply path. The combined output is governed as one power budget rather than as unrelated terminal loads.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE IC695PSD140E 40W 24V DC Power Supply |
| Item NO. | 2940706 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-18 |
A 40 W multi-purpose RX3i supply in the E hardware revision.
GE IC695PSD140E is the E-revision record of the PACSystems RX3i PSD140 multi-purpose power supply. It occupies one universal backplane slot, accepts a nominal 24 V DC source and provides a combined forty-watt load budget to the RX3i backplane.
The GE IC695PSD140E input operating range is 18 to 30 V DC. Front indicators report power, power-supply fault, overload and over-temperature conditions, while the design supports load sharing and redundant power-supply arrangements in supported RX3i configurations.
GE IC695PSD140E is the RoHS-compliant E hardware revision with the same fit, form and function as the preceding PSD140 design. Electrically, it feeds the RX3i backplane rails and reports internal fault, thermal and overload states to the controller fault system.
| Specification | IC695PSD140E |
|---|---|
| Brand | GE |
| Product name | PACSystems RX3i 40W multi-purpose DC power supply |
| Backplane position | One RX3i universal backplane slot |
| Nominal input | 24 V DC |
| Operating input range | 18 to 30 V DC |
| Total load rating | 40 W combined |
| Input-to-backplane isolation | No |
| Terminal conductor range | 14 to 22 AWG; one conductor per terminal |
| Front indicators | Power, P/S Fault, Overload, Overtemp |
| Redundancy feature | Supports load sharing / redundant supply arrangements |
| Operating temperature | 0 to 60 °C |
| Storage temperature | -40 to 85 °C |
| Relative humidity | 5 to 95% non-condensing |
| E revision | RoHS-converted release with unchanged fit, form and function |
The power path begins at the cabinet DC source and ends as several coordinated RX3i backplane rails.
IC695PSD140E converts the incoming DC source into the backplane voltages used by IC695 modules and the relay-output supply path. The combined output is governed as one power budget rather than as unrelated terminal loads.
In a supported multi-supply backplane, the modules share the active load and increase the available operating margin. The same architecture allows the backplane to remain powered when one supported supply path is lost.
Stored energy maintains valid outputs briefly when the input source dips. That behavior separates a momentary source interruption from a sustained loss that removes the backplane rails.
Four front indications divide source, internal, thermal and load conditions into distinct diagnostic states.
The POWER indication changes with source and switch conditions, so an illuminated module does not by itself prove that valid backplane power is being delivered. The controller fault table adds the system-level record.
An overload state means one or more backplane rails are approaching the supply limit. Electronic limiting protects the output path and the fault becomes visible to the RX3i controller.
The over-temperature indication represents internal thermal stress, which can arise from ambient heat, restricted airflow or sustained loading. It is separate from the red internal-fault state.
Moore Automation keeps power-supply enquiries tied to the installed rack and module load rather than using voltage alone. Exact revision, backplane identity, power budget, destination and required documentation can remain visible from quotation through receiving.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found