Input Refresh
Configured input modules place their state into the controller input data.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC693CPU370 CPU370 PLUS Controller |
| Item NO. | 2945441 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-26 |
GE Fanuc · Series 90-30
A 133 MHz Series 90-30 CPU with configurable RAM and flash storage for multi-baseplate control.
GE Fanuc IC693CPU370 is a CPU370 PLUS controller for Series 90-30 systems. Its 133 MHz processor executes the application and manages the I/O assigned across the CPU baseplate and supported expansion baseplates.
The 240 KB memory space of IC693CPU370 is configurable among program and data uses. Battery-backed RAM and flash storage provide two retention paths, so the controller startup selection and the contents stored in each medium must be preserved with the hardware configuration.
Unlike a CPU with built-in serial connectors, IC693CPU370 uses the Series 90-30 power-supply serial interface when that connection is required. The CPU also depends on a high-capacity supply and can coordinate a system of up to eight baseplates when expansion wiring and power budgets follow the platform rules.
| Technical Item | IC693CPU370 |
|---|---|
| Brand | GE Fanuc |
| Product Type | Series 90-30 CPU370 PLUS controller |
| Brand Country | United States |
| Processor | 133 MHz, 586 class |
| Configurable Memory | 240 KB |
| Storage | Battery-backed RAM and flash |
| Baseplate Capacity | Up to 8 total |
| Power Supply | High-capacity Series 90-30 supply required |
| Backplane Load | 7.4 W from 5 VDC |
| Floating Point | Hardware floating-point support |
| Built-in Serial Ports | None on CPU; power-supply port used |
| Program Features | Periodic subroutine support |
| Control Feature | I/O override support |
The IC693CPU370 scan ties a single application record to I/O distributed across the supported baseplates.
Configured input modules place their state into the controller input data.
The CPU executes the stored application against current register and I/O values.
The resulting output states are transferred to their assigned modules.
Baseplate links extend the I/O exchange while the CPU remains the system coordinator.
The CPU controls the local rack and supported expansion racks as one configured system. Each rack still needs a valid power and expansion path before its module data can participate in the scan.
Input data is captured before logic execution and output data is committed afterward. That sequence explains why a change detected during one scan is acted on in the controller’s defined scan order.
A CPU can retain its program while an expansion rack is unavailable. Rack status, cable continuity and the remote supply should be checked before editing logic that previously operated correctly.
An expansion-baseplate problem can leave the CPU program present while remote I/O is unavailable. Check the rack path and power state before changing the logic.
The controller record of IC693CPU370 depends on both memory allocation and the baseplate power environment.
Program and data uses share the configurable 240 KB memory space.
Battery-backed RAM preserves the working controller record while the retention circuit remains valid.
Flash can hold a nonvolatile record under the selected storage and startup settings.
A high-capacity supply provides the 5 V backplane power required by the CPU and installed modules.
The 240 KB space is divided among application and data uses according to controller configuration. Increasing one allocation can reduce the space available to another; it is not 240 KB for every memory class.
RAM is the working record protected by the retention system, while flash is nonvolatile storage. Startup behavior decides which record is used, so a saved flash copy can differ from the most recent RAM state.
The high-capacity supply powers the CPU and every installed module on the baseplate. The CPU requirement must be combined with the rest of the rack rather than checked as an isolated 7.4 W item.
A flash image and the active RAM record are not automatically identical. Record the startup source before replacing or power-cycling IC693CPU370.
IC693CPU370 has no built-in serial connector on the CPU face. Use the applicable Series 90-30 power-supply serial port and the correct cable and protocol settings.
Save the IC693CPU370 program, register allocation, hardware configuration, RAM or flash startup selection and expansion-baseplate arrangement before moving the CPU.
IC693CPU370 draws 7.4 W from the 5 V backplane and is specified for a high-capacity Series 90-30 supply. Include the remaining module loads in the baseplate power calculation.
Yes. IC693CPU370 can coordinate as many as eight baseplates in total when the Series 90-30 expansion arrangement, cables and supplies are correctly configured.
Treat the IC693CPU370 active RAM record and flash record as separate until they are deliberately synchronized. Confirm which source the CPU loads at startup before updating either one.
The verified IC693CPU370 record used here does not establish integrated Ethernet hardware. Do not assign Ethernet capability from a nearby CPU model; identify any communication module separately.
https://www.mvme.cn/
Moore Automation works with industrial automation product enquiries across controller, I/O, communication, drive and monitoring families. The company record links each request to the stated manufacturer, complete model and destination.
Moore Automation · Send the complete manufacturer, model and destination details through the contact channel that suits your request.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found