Home>B&R>B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules
B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules

B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules Item NO.: 2942572

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules
Item NO. 2942572
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category B&R
Brand B&R
Creation Time 2026-11-19

B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules
ATX20 Module

TEMPERATURE / RTD AND THERMOCOUPLE

B&R X20AT2222 / X20AT2402 X20 Temperature Input Modules

2temperature channels
01

Product Overview

B&R X20AT2222 and X20AT2402 are two-channel temperature input modules for the B&R X20 I/O system, but they convert different sensor principles. X20AT2222 supplies measurement current to Pt100 or Pt1000 resistance sensors in two- or three-wire circuits, while X20AT2402 measures J, K, N, S, B or R thermocouple voltage and applies internal terminal-temperature compensation.

The X20AT2222 terminal set separates Sensor+, Sense- and Sensor- so three-wire compensation can account for conductor resistance; a two-wire sensor joins the sense and return path according to the connection diagram. The X20AT2402 uses a differential TC+ / TC- pair and depends on correct thermocouple polarity and material from the junction to the terminal.

Both X20AT2222 and X20AT2402 multiplex enabled channels and let filtering determine measurement stability and update time, but their diagnostics describe different physical faults. Resistance range, wire compensation and excitation are central to X20AT2222, whereas open thermocouple conductors, cold-junction conditions and sensor-type selection are central to X20AT2402.

02

Product Data

Specification X20AT2222 X20AT2402
Brand B&R B&R
Product Name X20 Resistance Temperature Input Module X20 Thermocouple Input Module
Country Austria Austria
Input Quantity 2 2
Sensor Types Pt100 or Pt1000 J, K, N, S, B or R thermocouple
Measurement Principle Constant-current resistance measurement Differential thermocouple voltage
Field Wiring 2-wire or 3-wire 2-wire thermocouple pair
Lead Compensation 3-wire sense path Terminal-temperature compensation
Output Format INT temperature or UINT resistance INT temperature
Temperature Resolution Configurable sensor normalization 0.1°C or 0.01°C
Input Filter First-order low-pass, 500 Hz cutoff First-order low-pass, 500 Hz cutoff
Mains Rejection Configurable 50 Hz or 60 Hz Configurable 50 Hz or 60 Hz
Unused Channel Handling Can be disabled to reduce update time Can be disabled to reduce update time
Diagnostics Open line, overflow / underflow and channel state Open line, overflow / underflow and terminal compensation status
Operating Temperature -25 to 60°C horizontal; -25 to 50°C vertical -25 to 60°C horizontal; -25 to 50°C vertical
Required Station Parts X20BM11 and X20TB12 X20BM11 and X20TB12
03

Sensor Conversion Principles

The same temperature unit is produced from two different electrical quantities.

01

Resistance-to-temperature path

X20AT2222 drives a known current through the RTD and calculates resistance from the measured voltage. The configured Pt100 or Pt1000 characteristic then converts resistance to temperature, so sensor type and lead arrangement are inseparable from the result.

02

Thermoelectric-voltage path

X20AT2402 measures the thermocouple voltage created by dissimilar metals and combines it with terminal temperature. Reversed polarity or ordinary copper extension wire changes the voltage relationship before software scaling occurs.

03

Fault meaning differs

An open RTD loop on X20AT2222 interrupts the excitation path; an open thermocouple on X20AT2402 interrupts a low-level voltage source. Both can raise channel diagnostics, but the field tests and replacement sensors are not interchangeable.

04

Update-Time Management

Channel enable, sensor type and filtering determine how quickly a complete measurement cycle finishes.

01

RTD scan conditions

X20AT2222 update time changes with the number of active channels, the selected sensor types and filter time. Using different RTD types across two channels can require additional settling compared with one repeated characteristic.

02

Thermocouple scan conditions

X20AT2402 scans the enabled TC inputs and includes terminal compensation in the conversion path. Stronger mains rejection improves stability but extends the time before a new temperature is available.

03

Unused-channel discipline

Disabling unused channels on either module shortens the schedule and removes meaningless open-line alarms. The controller configuration should mirror the physical sensor count rather than leaving spare inputs active by default.

05

Questions About This Product

How do filter settings affect X20AT2222 and X20AT2402?

Both X20AT2222 and X20AT2402 trade response time for mains-noise rejection; select 50 Hz or 60 Hz and filter time from the installation instead of copying a setting without measuring the signal.

Which wiring difference makes X20AT2222 need a sense conductor while X20AT2402 does not?

X20AT2222 uses a three-wire sense path to compensate RTD lead resistance, whereas X20AT2402 uses the thermocouple pair and internal terminal-temperature compensation.

When X20AT2222 and X20AT2402 both show unstable values, which sensor paths should be inspected?

For X20AT2222, inspect RTD lead continuity, sensor type and excitation path; for X20AT2402, inspect thermocouple polarity, material, shielding and terminal thermal conditions.

What must be recorded before exchanging X20AT2222 or X20AT2402?

Record X20AT2222 RTD type, two-/three-wire scheme and filter, or X20AT2402 thermocouple type, polarity, resolution and filter before replacing the module.

Why should unused X20AT2222 and X20AT2402 channels be disabled?

Disabling unused channels on X20AT2222 and X20AT2402 reduces scan time and prevents open terminals from adding irrelevant diagnostics.

Can a Pt100 sensor be moved from X20AT2222 to X20AT2402?

No. X20AT2222 measures Pt100/Pt1000 resistance with excitation current, while X20AT2402 measures thermocouple voltage; use the correct module and wiring for the sensor principle.

06

Obsolete Parts Support

Moore Automation

https://www.mvme.cn

Moore Automation handles legacy part enquiries by preserving the original order number and the customer-supplied revision requirement.

Original identityThe legacy model remains the primary reference.
Revision awarenessRequested hardware or suffix details stay visible during review.
Alternative separationPotential alternatives are kept separate until the customer confirms scope.
Documentation continuityAvailable manuals and order records remain linked to the original item.

No related record found

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.