ON threshold
A closed loop must present 1 kΩ or less to the channel. Excess cable or contact resistance can leave a mechanically closed device outside the valid ON region.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Yokogawa SDV144-S5C/B4S10 16-Channel 24 V DC Safety Digital Input Module |
| Item NO. | 2932024 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | YOKOGAWA |
| Brand | YOKOGAWA |
| Creation Time | 2026-11-12 |
Yokogawa SDV144-S5C/B4S10 is a 16-channel 24 V DC contact-input module with module isolation for ProSafe-RS FIO. It interprets a field contact as ON at 1 kΩ or less and OFF at 100 kΩ or greater, using a nominal 6 mA input current from the external supply.
The S5C suffix of Yokogawa SDV144-S5C/B4S10 identifies the standard, non-explosion-protected pressure-clamp/MIL connection and the high-density -20 to +70 °C option. At the upper ambient range, the available input-channel count is restricted and must be reflected in the safety I/O layout.
Option /B4S10 on Yokogawa SDV144-S5C/B4S10 specifies the STB4S-10 surge-absorbing pressure-clamp terminal block for digital inputs. The module also supports field-wiring diagnostic elements, with SCB100 or SCB110 installed according to the normal state and diagnostic objective of each contact.
| Specification | SDV144-S5C/B4S10 |
|---|---|
| Brand | Yokogawa |
| Product Name | 16-Channel 24 V DC Safety Digital Input Module |
| Country | Japan |
| System family | ProSafe-RS / FIO |
| Input channels | 16, module isolation |
| Input signal | No-voltage contact |
| ON resistance | 1 kΩ maximum |
| OFF resistance | 100 kΩ minimum |
| Input current | 6 mA ±20 % |
| External power supply | 24 V DC +20 % / -10 %; 200 mA capacity |
| Maximum input voltage | 30.0 V DC |
| Input response time | 40 ms maximum |
| Current consumption | 290 mA at 5 V DC; 140 mA at 24 V DC maximum |
| Weight | Approx. 0.36 kg with pressure clamp/MIL cable |
| Connection option | /B4S10: STB4S-10 surge-absorbing input terminal block |
SDV144 evaluates the resistance of the complete field loop, so switch condition, wiring resistance and diagnostic elements are considered together.
A closed loop must present 1 kΩ or less to the channel. Excess cable or contact resistance can leave a mechanically closed device outside the valid ON region.
An open loop is recognized at 100 kΩ or greater. Leakage through suppression devices or wet wiring can keep the circuit below the valid OFF region.
The specified 40 ms maximum input response is combined with application filtering and task execution when determining the overall safety reaction time.
External diagnostic elements are selected from the normal contact state so the module can distinguish field wiring faults from legitimate process states.
SCB100 is connected in parallel with the field contact when the normal process state is OFF, supporting detection of a broken circuit while preserving state interpretation.
SCB110 is installed in series with correct polarity when the normal process state is ON, allowing short-circuit diagnostic behavior to be evaluated.
SCB100 and SCB110 can be used together for open- and short-circuit checking. Their resistance and polarity become part of the channel acceptance test.
For Yokogawa SDV144-S5C/B4S10, measure the total loop resistance at the terminal block. The closed path must be 1 kΩ or less, including contact, cable and diagnostic-element resistance.
Leakage or a parallel path can prevent Yokogawa SDV144-S5C/B4S10 from reaching the 100 kΩ OFF threshold. Inspect suppression devices, moisture, terminal contamination and the diagnostic-element connection.
Use SCB100 in parallel with the field contact on Yokogawa SDV144-S5C/B4S10 when the normal process state is OFF and open-circuit detection is required. Validate the resulting channel states.
SCB110 is a series diagnostic element for normally ON circuits, and Yokogawa SDV144-S5C/B4S10 expects the documented red/blue orientation. Reversed polarity can invalidate the intended diagnostic response.
Yokogawa SDV144-S5C/B4S10 uses suffix C. All sixteen channels are available through the lower ambient range, but only twelve are permitted at the highest stated temperature; apply the official limit to the cabinet design.
Verify that Yokogawa SDV144-S5C/B4S10 is connected through the STB4S-10 input terminal block, then test every channel for correct state, diagnostic behavior, surge path and terminal numbering.
Moore Automation provides enquiry support around exact automation-module identities, option codes and requested accessories. For safety I/O, the terminal-block option and full suffix are kept beside the module description.
The commercial record can also carry inspection photographs, packing requirements and delivery updates, helping customer teams compare the received channel module and termination hardware with the order.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found