Cscape assigns the I/O map from the SmartStack model and position. The map is not edited manually. Each output channel can be configured independently, including its output range and digital filter setting.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Horner HE800DAC106 SmartStack 4-Channel Analog Output Module |
| Item NO. | 2908081 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-09-14 |
HE800DAC106 is a SmartStack current-sourcing analog output module with four channels and 14-bit resolution. It converts controller data into 0–20.47 mA field signals and provides 10 VDC compliance for connected current loops.
Each channel is mapped as an analog output point, and the PLC update rate follows the controller scan rate. The removable spring-clamp terminal block carries four channel outputs, commons and shield terminations without an external module power supply.
| Technical Item | Specification Value |
|---|---|
| Brand | Horner |
| Model | HE800DAC106 |
| Product Type | SmartStack current-sourcing analog output module |
| Brand Country | United States |
| Channels | 4 |
| Output Range | 0–20.47 mA, including overrange |
| Resolution | 14 bits |
| Compliance / Peak Voltage | 10 VDC maximum |
| Maximum Loop Resistance | 500 Ω |
| Maximum Error at 25°C | 0.05% full scale |
| Additional Temperature Error | 0.005%/°C |
| Power | 3.3 W; 139 mA at 24 VDC |
| Operating Temperature | 0–60°C |
| Terminal | Removable spring clamp |
| Weight | 9.5 oz (270 g) |
Cscape assigns the I/O map from the SmartStack model and position. The map is not edited manually. Each output channel can be configured independently, including its output range and digital filter setting.
When the controller enters idle or stop mode, the default output value is zero. Module Setup can instead assign a specific value or hold the last value, so the stop-state behavior must be chosen deliberately for the process.
The four loops terminate as channel positive, common and shield connections. Shielded twisted-pair wiring is specified, with shields terminated at the terminal strip or directly at the panel ground block for severe applications.
The official wiring figure keeps each loop separate and shows the common shield arrangement. Open it to check the channel-by-channel pin pattern.
The default is zero output. Cscape Module Setup can assign a fixed stop value or hold the last value when the application requires different behavior.
Yes. The output range and filtering can be selected independently for each of the four channels.
Use shielded twisted-pair cable and terminate shields as specified for the panel environment.
No external module power supply is specified; required power is supplied through the SmartStack connection.
Confirm the configured current range and apply the documented conversion factor so the controller data represents the intended loop current.
Moore Automation supports catalog-specific enquiries for industrial automation products. Customers can request 100% original products with fast delivery, a 1-year warranty and a 12-hour online response.
Send the complete catalog number and required quantity for product identification and order assistance.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found