Welcome to Moore Automation Limited

0
Loadding...
 

sales@mvme.cn    Phone: +86 18030175807

Home>GE>GE IC695MDL754 32-Point DC Output Module
GE IC695MDL754 32-Point DC Output Module

GE IC695MDL754 32-Point DC Output Module Item NO.: 2907977

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name GE IC695MDL754 32-Point DC Output Module
Item NO. 2907977
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category GE
Brand GE
Creation Time 2026-09-13

GE IC695MDL754 32-Point DC Output Module
PACSystems RX3i I/O

GE IC695MDL754 32-Point DC Output Module

12/24 VDC positive-logic outputs, arranged as two isolated 16-point groups for RX3i control architectures.

Product Overview

The GE IC695MDL754 is a 32-point DC discrete output module for the PACSystems RX3i platform. It uses positive-logic output switching and divides the field interface into two isolated groups of 16 outputs.

IC695MDL754 installs in any RX3i I/O slot and is used with an RX3i CPU release 2.90 or later. The module exchanges commanded output states over the RX3i backplane while its field circuits are supplied from an external 12 to 30 VDC source.

Each output point is rated for 0.75 A. The module combines optical field-to-backplane isolation with group-to-group isolation, separating the field wiring from the backplane and the two output groups. It is intended for DC field loads within the published voltage, current, and thermal limits.

Technical Data

BrandGE
Brand headquartersUnited States
ModelIC695MDL754
Product type32-point DC output module
Rated voltage12/24 VDC nominal
Output voltage range10.2 to 30 VDC
Output arrangement32 points; two isolated groups of 16
LogicPositive logic
Output current0.75 A per point
External power+12 to +30 VDC; 12/24 VDC nominal
Backplane consumption300 mA maximum from the 5 V bus
Module ID0x059h
Output voltage drop0.3 VDC maximum
Output leakage0.1 mA maximum
Response time0.5 ms maximum, on and off
Isolation250 VAC continuous; 1500 VAC for 1 minute

Installation

  1. Confirm that the controller is an RX3i CPU running release 2.90 or later. IC695MDL754 is not used with a Series 90-30 PLC CPU.
  2. Install the module in an available RX3i I/O slot.
  3. Wire outputs 1–16 and 17–32 as their separate 16-point field groups, connecting each group to its own DC+ and DC− field-power terminals.

Diagnostics

  • If only part of the field wiring is affected, first identify whether the issue is in the 1–16 or 17–32 output group, then check that group’s DC+ and DC− field-power connections.
  • For an output that does not respond as commanded, check the associated field load and wiring for a short-circuit condition; IC695MDL754 provides electronic short-circuit protection.
  • When the application operates at 30 VDC in a warm enclosure, review the RX3i manual’s published derating curve before increasing the output loading.
Configuration boundary: IC695MDL754 is for an RX3i system and requires an RX3i CPU release 2.90 or later; it is not for use with a Series 90-30 PLC CPU.

Product FAQ

I am replacing a failed IC695MDL754 module. How do I avoid a controller compatibility problem?

Confirm the order code is IC695MDL754 and that the host is an RX3i CPU at release 2.90 or later. IC695MDL754 is not for use with a Series 90-30 PLC CPU.

A group of devices driven by IC695MDL754 is not actuating. Where should I begin?

For IC695MDL754, separate the affected points into the 1–16 or 17–32 group, then verify the corresponding group’s DC+ and DC− field-power connections before investigating individual loads.

An IC695MDL754 output does not follow the controller command after wiring. What should be checked?

For IC695MDL754, review the field-device wiring and load on that output point, then confirm the output belongs to the intended 16-point group. This keeps field-side troubleshooting separate from the RX3i backplane connection.

How should I respond when a shorted field load is suspected on IC695MDL754?

Isolate the field load connected to IC695MDL754 and inspect its cable path and wiring before returning it to service. IC695MDL754 includes electronic short-circuit protection, but the field-side cause still needs to be corrected.

What should I consider before running IC695MDL754 at 30 VDC in a warm cabinet?

For IC695MDL754, use the published RX3i derating curve for the expected ambient temperature and output loading. The manual identifies derating above 42 °C when operating at 30 VDC.

How can I plan a like-for-like IC695MDL754 spare for a critical machine?

Record the full IC695MDL754 model number, the RX3i CPU release, and which field devices are connected to each 16-point output group. This gives maintenance staff the key compatibility and wiring context for replacement planning.

Moore Automation Supply Focus

Moore Automation supplies industrial automation parts for control-system maintenance and replacement planning, including PLC, DCS, HMI, drive, and related automation components.

  • Original products
  • Fast delivery
  • 1-year warranty
  • 12-hour online response
Moore Automation warehouse team member preparing stocked industrial automation parts

Contact Us

ManagerLeonia
WhatsApp+8618030175807

No related record found

You May Also Like

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.