Welcome to Moore Automation Limited

0
Loadding...
 

sales@mvme.cn    Phone: +86 18030175807

Home>GE>GE IC693PWR322E Series 90-30 24/48 V DC Power Supply
GE IC693PWR322E Series 90-30 24/48 V DC Power Supply

GE IC693PWR322E Series 90-30 24/48 V DC Power Supply Item NO.: 2943302

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name GE IC693PWR322E Series 90-30 24/48 V DC Power Supply
Item NO. 2943302
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category GE
Brand GE
Creation Time 2026-11-20

GE IC693PWR322E Series 90-30 24/48 V DC Power Supply
GESERIES 90-30 POWER
Thirty-watt rack power conversion

GE IC693PWR322E Series 90-30 24/48 V DC Power Supply

DC input power for controller logic, relay and isolated field circuits.

Product facts

Product Description

IC693PWR322E is a 30 W Series 90-30 power supply for 24 V DC or 48 V DC nominal input. It plugs into the dedicated left position of the baseplate and converts the incoming source into the rack power rails used by the CPU and installed modules.

The input of IC693PWR322E operates from 18 to 56 V DC after startup and requires at least 21 V DC to start. Its outputs include the 5 V DC logic rail, a 24 V DC relay-power rail and an isolated 24 V DC source that can serve compatible modules or external input circuits.

Front terminals on IC693PWR322E provide the polarity-sensitive DC input and isolated 24 V DC output connections. Status indicators report supply health together with CPU RUN and battery state because the power-supply face also carries the Series 90-30 serial and battery interfaces.

IC693PWR322 power capacity and front terminal arrangement
Reference values

Product Specifications

Brand
GE
Model
IC693PWR322E
Product Name
Series 90-30 24/48 V DC Power Supply
Country
Not specified
Series
Series 90-30
Nominal Input
24 or 48 V DC
Start Range
21 to 56 V DC
Run Range
18 to 56 V DC
Maximum Input Power
50 W at full load
Total Output Capacity
30 W
5 V DC Capacity
15 W
Isolated 24 V DC Capacity
20 W
Relay 24 V DC Capacity
15 W
5 V Overcurrent Limit
4 A maximum
5 V Overvoltage Limit
6.4 to 7 V
Holdup Time
14 ms minimum
Product behavior

Operating Characteristics

IC693PWR322E converts one DC source into three output functions that share a 30 W total limit.

STARTUP

Require adequate input before conversion begins

The supply will run down to 18 V DC after starting, but initial input must reach the higher start threshold.

LOAD SHARING

Apply individual and total limits together

Each rail has its own capacity, while the combined load of all outputs may not exceed the overall 30 W rating.

HOLDUP

Bridge short input interruptions

Stored energy maintains the outputs for a minimum interval so the controller does not react to every brief source disturbance.

System context

Diagnostics and Protection

IC693PWR322E indicators and measured rails separate source, supply and controller conditions.

SOURCE

Measure input at the loaded terminals

A nominal source can sag below the start or run limit at the power-supply connector when wiring or upstream capacity is inadequate.

OUTPUTS

Check rails by function

The 5 V logic rail, relay power and isolated 24 V output serve different loads, so an overload must be traced to the affected path.

STATUS

Read supply and controller indications together

PWR, OK, RUN and battery information on the front panel shows whether the fault begins with conversion, CPU execution or retained-memory support.

Practical checks

Common Questions

What records help diagnose an intermittent IC693PWR322E reset?

Capture IC693PWR322E input voltage, PWR/OK/RUN LEDs, total rack load, source events and the controller fault time.

Why will IC693PWR322E not start from an 18 V source?

IC693PWR322E can continue running at 18 V DC but needs at least 21 V DC for startup; measure the input at the loaded terminals.

How is polarity checked on IC693PWR322E?

IC693PWR322E is a DC-input-only supply, so verify plus and minus at the front terminals before energizing.

What should be added before calculating IC693PWR322E capacity?

For IC693PWR322E, total every module load on 5 V, isolated 24 V and relay 24 V, then apply both the individual rail limits and 30 W combined limit.

Which output on IC693PWR322E serves relay modules?

The dedicated 24 V relay-power output on IC693PWR322E supplies compatible Series 90-30 relay-output circuits; it is distinct from the isolated 24 V source.

Why does IC693PWR322E shut down when an input circuit is shorted?

A short on the isolated 24 V output can overload IC693PWR322E and stop the PLC; isolate the field branch before restoring power.

Moore Automation

Reasons to Choose Us

Moore Automation

https://www.mvme.cn/

Moore Automation keeps a power-supply enquiry with one sales contact from model review through quotation and available tracking communication. For IC693PWR322E, the full suffix, Series 90-30 context, quantity and destination stay visible without adding unsupported compatibility claims.

Account continuity
Named contact for the enquiry
Technical identity
Model and rack family retained
Commercial clarity
Quotation and tracking records
Moore Automation company information image
CompanyMoore Automation
ManagerLeonia

No related record found

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.