Each output common is protected by a user-replaceable 3.15 A fuse, and each AC output includes an RC snubber for power-line transients. Because a fuse protects a group common, one blown fuse disables every output in that group.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC200UAA007 VersaMax 28-Point AC I/O Micro PLC |
| Item NO. | 2908087 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-09-14 |
IC200UAA007 is a 28-point VersaMax Micro PLC with sixteen 120 VAC inputs and twelve 120/240 VAC triac outputs. The controller operates from a 100–240 VAC supply and is designed for AC field devices rather than DC input circuits.
The outputs are arranged in isolated groups with separate commons, allowing groups to use different phases or a common source. Replaceable common fuses and individual RC snubbers provide group protection and transient suppression for the AC output path.
| Technical Item | Specification Value |
|---|---|
| Brand | GE Fanuc |
| Model | IC200UAA007 |
| Product Type | VersaMax 28-point AC I/O Micro PLC |
| Brand Country | United States |
| Inputs / Outputs | 16 AC inputs / 12 AC outputs |
| Controller Power | 85–264 VAC |
| Power Frequency | 47.5–63 Hz |
| Input Voltage | 85–132 VAC, 50/60 Hz |
| Input Current | 8 mA RMS at 100 VAC, 60 Hz |
| Input Response | 25 ms max ON; 30 ms max OFF |
| Output Voltage | 85–264 VAC, 47.5–63 Hz |
| Resistive Output Load | 0.5 A per point |
| Output Response | 1 ms max ON; 1/2 cycle + 1 ms max OFF |
| Isolation | 1500 V RMS field-to-logic; 500 V RMS between groups |
| Weight | 600 g (1.32 lb) |
Each output common is protected by a user-replaceable 3.15 A fuse, and each AC output includes an RC snubber for power-line transients. Because a fuse protects a group common, one blown fuse disables every output in that group.
The fuse state must therefore be checked at group level when several outputs stop together, after power has been removed in accordance with the controller procedure.
The sixteen inputs require an AC field source and cannot be driven from DC. Output commons are isolated, so each group can be assigned to a different AC phase or to the same supplied phase.
The wiring figure shows the input commons, fused output groups and external AC load sources. Open it to verify group boundaries before transferring panel conductors.
No. The reactive input circuits require an AC source and are not specified for DC operation.
Each replaceable fuse protects a common shared by several outputs, so a blown fuse can disable an entire output group.
Yes. The isolated commons allow separate phases, provided each group is wired within its documented ratings.
No. This AC I/O model does not provide high-speed counter, PWM or pulse-train operation.
Confirm the 120 VAC input requirement, triac output load, common grouping and 100–240 VAC controller supply.
Moore Automation supplies identified automation parts for maintenance and replacement needs. The offering includes difficult-to-source products, 100% original products and a 1-year warranty.
Send the complete catalog number and required quantity for product identification and order assistance.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found