Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | General Electric IS200ESELH2A Exciter Selector Board |
| Item NO. | 2907252 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-09-11 |
The IS200ESELH2A is an Exciter Selector Board (ESEL) from GE's EX2100 static excitation system. It functions as the central pulse-routing hub for multi-bridge power converter configurations.
The H2 model is engineered to synchronize and manage gate trigger commands for up to three parallel Power Conversion Modules (PCMs). It receives six logic-level gate pulse signals from its associated EMIO board and replicates them to three separate output channels, ensuring identical firing angles across all parallel bridges .
In redundant configurations, two IS200ESELH2A boards operate in parallel (one driven by M1, one by M2), with controller C determining the active master. The standby board has all outputs blocked, guaranteeing only one controller commands the multi-bridge array at any time.
| Parameter | Value |
|---|---|
| Brand | General Electric (GE) |
| Model | IS200ESELH2A |
| Type | Exciter Selector Board (ESEL) |
| Country | United States |
| Series | EX2100 / Mark VI Excitation Control |
| ESEL Group | H2 |
| Bridge Drivers | 3 |
| Power Conversion Modules | Up to 3 PCMs |
| Gate-Pulse Outputs | 6 signal cable sets |
| Input Signal | Logic-level gate-pulse signals from EMIO |
| Output Interface | EGPA boards |
| Redundant Operation | Supported (two ESEL boards, M1 + M2) |
| Connectors | P1, P2 |
| Front LEDs | Power / Session / Gating status |
| Failover Time | < 10 ms automatic switch |
| Power Draw | < 5 W typical, < 8 W max |
| Operating Temperature | -40°C to +70°C |
| Humidity | 5% – 95% non-condensing |
| Isolation | 2.5 kV AC field-to-logic |
| Communication | EISB exciter internal serial bus |
The IS200ESELH2A receives a single set of six logic-level gate pulse signals from its associated EMIO board, representing the firing commands for a conceptual three-phase bridge. It then replicates and routes this single set of six pulses to output channels for up to three separate PCMs.
In Triple Modular Redundant (TMR) systems, the IS200ESELH2A performs critical arbitration for the entire set of bridges under its control. Two ESEL boards operate in parallel, with controller C determining the active master.
Moore Automation supports power generation and heavy industry with a focus on legacy excitation control components. Our team helps plants maintain GE EX2100 and Mark VI excitation systems when OEM support windows close and replacement parts become scarce.
With a global sourcing network, we locate discontinued exciter selector boards and related components, verifying revision levels and bridge-driver configuration before shipment. Our process is built for the reality of forced outages — fast quotes, clear condition reports, and shipping that meets your maintenance window.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found