Junction
The thermocouple creates a small voltage related to the difference between its measuring and reference junctions.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC200ALG630-GD Thermocouple Input Module |
| Item NO. | 2945440 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-26 |
GE Fanuc · VersaMax
Seven individually converted channels for thermocouple or low-level millivolt measurement with cold-junction compensation.
GE Fanuc IC200ALG630-GD is a seven-channel VersaMax analog input module for thermocouple and millivolt signals. Each field pair feeds its own conversion path, allowing the controller to receive temperature or low-level voltage data without an external signal conditioner for the supported ranges.
For thermocouple operation, IC200ALG630-GD combines the measured junction voltage with cold-junction temperature from built-in carrier thermistors. The module can also use an applicable external thermistor arrangement, and the selected configuration determines how terminal temperature is included in the reported value.
Channel diagnostics in IC200ALG630-GD distinguish an open circuit, range violation, configured high or low alarm and thermistor fault. Each point is converted in sequence, so the complete update time follows the configured line-frequency rejection and the seven active channel conversions rather than a single simultaneous sample.
| Technical Item | IC200ALG630-GD |
|---|---|
| Brand | GE Fanuc |
| Product Type | VersaMax thermocouple and millivolt input module |
| Brand Country | United States |
| Input Channels | 7, independent |
| Thermocouple Types | J, K, T, S and R |
| Millivolt Ranges | ±19.5, ±39, ±78.125, ±156.25, ±312.5 and ±625 mV |
| Resolution | 16 bit; 15 bits plus sign |
| Power Source | Backplane powered; no external supply required |
| Cold-Junction Compensation | Built-in thermistors; supported external arrangement |
| Diagnostics | Open circuit, overrange, underrange, alarms and thermistor fault |
| 60 Hz Conversion Time | 60 ms per point |
| 50 Hz Conversion Time | 70 ms per point |
| Isolation | 250 VAC continuous field-to-logic |
| GD Revision Record | Compatibility and functionality update, August 2009 |
A temperature value from IC200ALG630-GD is produced from both the sensor voltage and the terminal-junction temperature.
The thermocouple creates a small voltage related to the difference between its measuring and reference junctions.
The sensor pair reaches one module channel through the compatible VersaMax carrier.
Cold-junction temperature is combined with the measured voltage for the selected thermocouple type.
The corrected value is scaled into the channel data delivered to the controller.
A thermocouple voltage represents the difference between the measuring junction and the terminal reference. The module needs both the low-level voltage and the cold-junction temperature to calculate the reported process temperature.
J, K, T, S and R sensors do not share one conversion curve. Selecting the wrong type can produce a smooth but incorrect reading because the same measured voltage is interpreted through different thermocouple tables.
The seven channels are converted in sequence with the selected 50 or 60 Hz rejection timing. A complete module sweep therefore grows with the number of active points rather than occurring as one simultaneous sample.
Thermocouple type and wiring polarity must agree with the configured channel. Reversing the pair or choosing the wrong type can create a plausible but incorrect temperature value.
The diagnostics of IC200ALG630-GD follow the measurement path instead of acting as a single module-level flag.
The carrier temperature reference is checked before compensation is applied.
Open-circuit detection watches for a broken or disconnected sensor path.
The converted value is compared with the selected measurement span.
Configured high and low thresholds can identify a process value outside the intended band.
Built-in carrier thermistors measure the terminal-area temperature used for compensation. An applicable external reference arrangement changes where that temperature information originates, not the basic thermocouple polarity.
An open-circuit status identifies the sensor path, while a thermistor fault identifies the compensation reference. They require different wiring checks even when both can make the reported temperature unusable.
High and low alarms compare the converted engineering value with configured thresholds. They supplement the measured channel data and should not be mistaken for electrical overrange or underrange diagnostics.
A thermistor fault and an open thermocouple describe different parts of the chain. Read the channel diagnostic code before replacing the sensor.
IC200ALG630-GD supports J, K, T, S and R thermocouples. The configured type must match the connected sensor because each type uses a different voltage-to-temperature relationship.
IC200ALG630-GD uses a carrier temperature reference for cold-junction compensation. A thermistor or carrier-reference problem is separate from continuity of the field thermocouple itself.
No. IC200ALG630-GD is powered from the VersaMax backplane. Its low-level sensor inputs do not require a module field-power supply.
IC200ALG630-GD converts points sequentially at 60 ms per point for 60 Hz rejection or 70 ms per point for 50 Hz rejection. Multiply the configured per-point time by the active channel count when estimating a full sweep.
Yes. IC200ALG630-GD supports multiple bipolar millivolt spans as well as the documented thermocouple types. Choose the channel mode and range that match the source signal.
The GD record for IC200ALG630-GD is associated with an August 2009 compatibility and functionality update. Preserve GD in the hardware record when comparing configuration support or a spare.
https://www.mvme.cn/
Moore Automation can review requests for mature automation families by keeping the original manufacturer code, installed platform and requested revision together. The process focuses on identification and available documentation rather than assuming interchangeability.