Controller positions
KL4002X1-BA1 places the primary and optional redundant controller in two central positions, each connected to the carrier power and network structure.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Emerson DeltaV KL4002X1-BA1 PK Controller Carrier |
| Item NO. | 2944587 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | EMERSON |
| Brand | EMERSON |
| Creation Time | 2026-11-24 |
PK Controller Carrier
Emerson DeltaV KL4002X1-BA1 is the horizontal DIN-rail carrier for a DeltaV PK Controller node. It provides the mechanical and electrical interface for one or two PK controllers, the associated power modules, six Ethernet connections and the LocalBus connection leading to traditional I/O carriers.
Primary and secondary 24 VDC inputs enter KL4002X1-BA1 through separate carrier terminals. The carrier distributes controller power, provides 12.25 VDC for connected I/O card carriers and divides the six full-duplex 10/100BASE-TX ports into left and right groups around the controller positions.
The physical key switch on KL4002X1-BA1 changes which controller-management actions are permitted, while the carrier connector continues the I/O path to the next subsystem. Backup-battery terminals, power-module positions and the two controller positions remain distinct, so their functions can be traced from the numbered front arrangement.
| Attribute | KL4002X1-BA1 |
|---|---|
| Brand | Emerson DeltaV |
| Product Name | PK Controller carrier |
| System | DeltaV PK Controller |
| Controller capacity | Two PK controllers |
| Node arrangements | Simplex or 1:1 redundant |
| Input power, redundant | 24 VDC ±10%, 2.75 A maximum |
| Output to I/O card carriers | 12.25 VDC, 3.0 A maximum |
| Ethernet connections | Six redundant RJ45 ports |
| Ethernet physical layer | 10/100BASE-TX, full duplex |
| Port power from controller | 5.0 VDC, 200 mA maximum per port |
| Carrier port-power support | 5.0 VDC, 300 mA maximum |
| Mounting | Upright on horizontal DIN rail |
| Power terminal groups | Primary and secondary |
| Local I/O interface | Carrier connector to I/O card carriers |
| Physical access control | On-carrier key switch |
The carrier joins the node mechanically, but its power, Ethernet and LocalBus circuits remain identifiable from their connectors.
KL4002X1-BA1 places the primary and optional redundant controller in two central positions, each connected to the carrier power and network structure.
Ports 1-3 and 4-6 sit on opposite sides of KL4002X1-BA1. The two groups let primary and secondary network paths remain physically distinguishable.
The right-side carrier connector on KL4002X1-BA1 continues power and communication toward connected traditional I/O card carriers.
Power-module placement, separate input terminals and the key switch address different parts of node availability and administration.
KL4002X1-BA1 accepts primary and secondary 24 VDC wiring at separate terminals, allowing the carrier to feed its controller and I/O power structure.
The power-module positions on KL4002X1-BA1 supply connected I/O through the carrier. Their role is separate from the 24 VDC consumed by the controller modules.
When the physical key on KL4002X1-BA1 is locked, download, decommission, upgrade and Telnet actions are blocked while authentication and supported project retrieval remain available.
Because KL4002X1-BA1 is the shared carrier, inspect its primary and secondary power terminals, controller seating, carrier connector and network-port groups before treating the condition as two independent controller faults.
The locked position on KL4002X1-BA1 blocks download, decommission, upgrade and Telnet operations; it does not replace controller authentication or remove carrier power.
For KL4002X1-BA1, record ports 1-3 and 4-6 by side, cable destination, assigned subsystem and primary or secondary network role.
KL4002X1-BA1 distributes 12.25 VDC toward connected I/O carriers through a path distinct from controller input power, so a controller can be powered while the downstream I/O supply requires separate review.
KL4002X1-BA1 mounts upright on a horizontal DIN rail; the controller, power-module and I/O-carrier connections must remain accessible in that orientation.
Provide the full KL4002X1-BA1 code, simplex or redundant arrangement, controller and power-module codes, network-port assignments, LocalBus connections and clear carrier photographs.
Moore Automation organizes industrial-control enquiries by complete manufacturer code and installed assembly position. Controller, carrier, power and network details remain separated so nearby DeltaV parts are not merged during review.
A named contact coordinates requested documents, quotation information and shipment updates while photographs and model corrections remain attached to the enquiry record.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found