Scheduled control logic
KL2002X1-BA1 runs assigned control modules at scan rates selected for the process. Input values are read before the scheduled logic calculates the corresponding outputs.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Emerson DeltaV KL2002X1-BA1 PK100 Controller |
| Item NO. | 2944586 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | EMERSON |
| Brand | EMERSON |
| Creation Time | 2026-11-24 |
PK100 Controller
Emerson DeltaV KL2002X1-BA1 is the PK100 controller module in the DeltaV PK Controller family. It executes control logic from local I/O and Ethernet-device signals, schedules control modules at their assigned scan rates and returns calculated outputs through the controller carrier to the connected I/O and network paths.
The PK100 capacity of KL2002X1-BA1 provides 100 device signal tags, up to 16 Ethernet devices on port P01 and a PROFINET device limit that depends on the installed DeltaV version. The same controller can operate as a simplex node or as one member of a 1:1 redundant pair mounted beside a second controller on the PK carrier.
Power for KL2002X1-BA1 enters through the carrier as 24 VDC, while project and restart information can be retained on a removable 2 GB or 8 GB SDHC card. The card becomes physically accessible only after the controller is removed from the carrier, so the controller module, carrier key state and stored project remain separate parts of the hardware boundary.
| Attribute | KL2002X1-BA1 |
|---|---|
| Brand | Emerson DeltaV |
| Product Name | PK100 controller |
| Controller family | DeltaV PK Controller |
| Licensed capacity | 100 device signal tags |
| Ethernet devices on P01 | Maximum 16 |
| PROFINET devices, v15.FP1/FP2 | Maximum 50 |
| PROFINET devices, v15.FP3 or later | Maximum 100 |
| Standalone batch units | Maximum 2 |
| Control-module scan range | 25 ms to 60 s |
| Input power through carrier | 24 VDC ±10%, 350 mA maximum |
| Redundant pair input current | 700 mA maximum |
| Power dissipation | 7.5 W simplex; 15 W redundant pair |
| RTC backup input | 5.0 to 12.6 VDC, 15 µA typical simplex |
| Removable memory | SDHC v2.0, 2 GB or 8 GB |
| Operating temperature | -40 to 60°C |
The control schedule, LocalBus and Ethernet paths work together, but each carries a different part of the control cycle.
KL2002X1-BA1 runs assigned control modules at scan rates selected for the process. Input values are read before the scheduled logic calculates the corresponding outputs.
Through its carrier, KL2002X1-BA1 exchanges data with connected traditional I/O carriers. The LocalBus can extend across as many as eight carriers and 64 traditional I/O cards.
KL2002X1-BA1 uses the carrier network ports for Ethernet device control. P01 can carry Modbus TCP client or EtherNet/IP traffic while PN1 provides the PROFINET controller path.
Controller size defines the licensed signal capacity, while node availability and stored project data are handled by separate hardware relationships.
KL2002X1-BA1 identifies the 100-DST controller size. Ethernet and PROFINET device limits remain additional limits rather than replacements for the DST capacity.
A second KL2002X1-BA1 can occupy the adjacent carrier position for 1:1 redundancy. Both modules receive their power and network access through the common carrier arrangement.
The removable SDHC card in KL2002X1-BA1 retains the controller project used for a supported simplex controller swap. Physical removal from the carrier is required before the card can be reached.
KL2002X1-BA1 has separate limits for 100 device signal tags, Ethernet devices and PROFINET devices, so review the licensed DST use as well as the network-device count.
For KL2002X1-BA1, verify the saved project, controller state, carrier key position and SDHC card before removing power; the supported restart procedure transfers the card to the replacement controller.
KL2002X1-BA1 also depends on correct carrier seating, the physical key state, project authentication, network configuration and controller diagnostics, so supply voltage alone does not establish a running node.
Record whether KL2002X1-BA1 is installed as simplex or as one member of a 1:1 pair, then capture both controller plates, carrier positions and power-module arrangement.
For KL2002X1-BA1, PK100 identifies a capacity of 100 device signal tags; it does not describe the number of physical terminals or the carrier Ethernet-port count.
Include the complete KL2002X1-BA1 code, DeltaV version, simplex or redundant arrangement, DST use, SDHC capacity, carrier code and clear controller/carrier photographs.
Moore Automation keeps controller, carrier and power-module codes on separate enquiry lines while retaining photographs of the assembled node. This makes the exact hardware boundary visible before commercial information is prepared.
Requested documentation, quotation details and shipment communication are coordinated through one named account contact, with configuration corrections recorded against the same enquiry.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found