Product Name B&R X20AT6402 X20 Thermocouple Input Module
Item NO. 2942563
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category B&R
Brand B&R
Creation Time 2026-11-19

B&R X20AT6402 X20 Thermocouple Input Module
ATX20 Module

TEMPERATURE / THERMOCOUPLE INPUT

B&R X20AT6402 X20 Thermocouple Input Module

6thermocouple channels
01

Product Introduction

B&R X20AT6402 is a six-channel thermocouple input module for the B&R X20 I/O system. It accepts J, K, N, S, B and R sensors, measures the millivolt signal at each channel, compensates the junction temperature at the terminal area and transfers normalized temperature values and channel status to the controller.

All six inputs of X20AT6402 pass through a multiplexer to a shared A/D conversion path, so the number of enabled channels and the selected mains-frequency filter determine the complete update time. Channels that are not required can be disabled, while the filter and 0.1°C or 0.01°C resolution are configured for the measurement task instead of being treated as independent nameplate values.

The X20AT6402 terminal arrangement pairs TC+ and TC- conductors for each sensor and uses internal terminal-temperature measurement for cold-junction compensation. For ceramic heating elements with integrated thermocouples, the minus input is tied to the supply-feed minus as shown in the official connection scheme to reduce ripple-related measurement error.

02

Technical Information

Brand B&R
Model X20AT6402
Product Name X20 Thermocouple Input Module
Country Austria
Input Quantity 6 thermocouple inputs
Supported Sensor Types J, K, N, S, B and R
Measurement Path Multiplexed differential inputs with A/D conversion
Terminal Compensation Integrated terminal-temperature measurement
Resolution Configurable 0.1°C or 0.01°C for sensor temperature
Input Filter First-order low-pass, 500 Hz hardware cutoff
Mains Rejection Configurable 50 Hz or 60 Hz filtering
Channel Update Depends on enabled-channel count and filter selection
Status Information Per-channel overflow, underflow and open-line indication
Isolation Channel group isolated from X20 bus
Operating Temperature -25 to 60°C horizontal; -25 to 50°C vertical
Required Station Parts X20BM11 and X20TB12
Degree of Protection IP20
03

Cold-Junction Compensation Path

The measured temperature combines sensor voltage with the temperature at the field termination.

01

Thermocouple millivolt input

Each TC pair produces a small voltage determined by the temperature difference along the thermocouple materials. Polarity, sensor type and extension-wire material must remain consistent from the sensing junction to the X20AT6402 terminal.

02

Terminal-temperature measurement

The module measures the terminal area and applies that value to the selected thermocouple characteristic. Heat sources near the terminal or a loose terminal block can disturb compensation even when the remote sensor itself is intact.

03

Normalized controller value

After compensation and filtering, X20AT6402 delivers the configured temperature resolution plus status information. The application should reject overflow, underflow or open-line results before using the numeric value in control calculations.

04

Channel Scheduling and Filtering

One conversion path serves six channels, so channel enable and filter settings define when a new valid value is available.

01

Enabled-channel sequence

The multiplexer advances through the enabled inputs in the configured order. Disabling unused X20AT6402 channels shortens the complete scan and prevents disconnected terminals from adding open-line states that do not belong to the installed sensor set.

02

Mains-frequency rejection

The selected 50 Hz or 60 Hz filter suppresses interference related to the local supply system. A stronger filtering choice increases update time, so the setting must match both noise conditions and the required control response.

03

Stable wiring reference

Thermocouple conductors should be routed away from switching power and kept as matched material pairs. For integrated heater thermocouples, the documented minus-reference connection prevents supply ripple from being added to the measured signal.

05

Frequently Asked Questions

Which X20AT6402 settings must match a replacement thermocouple to avoid a plausible but wrong value?

For X20AT6402, verify the configured J, K, N, S, B or R type, thermocouple polarity and extension-wire material; a sensor can be connected yet produce a plausible but incorrect value when the characteristic is mismatched.

When X20AT6402 reports an open line, which physical connections should be tested?

On X20AT6402, inspect both TC conductors, terminal seating, cable continuity and the sensor junction before disabling the diagnostic or substituting a value.

How can unused X20AT6402 inputs affect commissioning?

Unused X20AT6402 channels should be disabled; leaving an open channel active adds scan time and can present open-line status that is unrelated to the connected sensors.

What makes an X20AT6402 channel respond more slowly after filtering is increased?

X20AT6402 multiplexes enabled channels and applies the selected 50 Hz or 60 Hz filtering, so the complete update time grows with active-channel count and filter time.

Why can X20AT6402 values shift when cabinet temperature changes?

X20AT6402 uses terminal-temperature compensation, so inspect airflow, nearby heat sources and terminal-block seating when all thermocouple values shift together with cabinet temperature.

Where should an integrated heater thermocouple be referenced on X20AT6402?

Wire X20AT6402 according to the documented heater scheme, including the thermocouple minus connection to the supply-feed minus, so supply ripple is not added to the measurement path.

06

Technical Enquiry Handling

Moore Automation

https://www.mvme.cn

Moore Automation records the requested model and associated technical questions before preparing a commercial response.

Exact part referenceManufacturer, model and suffix are captured without shortening the order string.
Document alignmentAvailable technical documents are matched to the requested part identity.
Question trackingConnection, revision and accessory questions remain tied to the enquiry line.
Commercial separationTechnical identity is confirmed before price and delivery information are finalized.

No related record found

You May Also Like

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.