Welcome to Moore Automation Limited

0
Loadding...
 

sales@mvme.cn    Phone: +86 18030175807

Home>AB>Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches
Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches

Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches Item NO.: 2910060

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches
Item NO. 2910060
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category AB
Brand ALLEN-BRADLEY
Creation Time 2026-09-21

Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches

Allen-Bradley · Stratix 5200

Allen-Bradley 1783-CMS20DP / 1783-CMS20DN Stratix 5200 20 Port Managed Switches

20-port managed switch pair

Catalog number1783-CMS20DP / 1783-CMS20DN
Product class20-port managed switch pair

Product Profile

Within a Stratix 5200 control-network layer, Allen-Bradley 1783-CMS20DP and 1783-CMS20DN provide the same high-port-density managed switching foundation for machine cells, cabinet-to-cabinet links, and network segments that combine copper devices with uplink media. Their shared role is to collect industrial Ethernet connections while retaining management and resilience functions at the switch layer.

The pair belongs to the same Stratix 5200 system family and uses the same twenty-port hardware class. This makes the models relevant where a project needs a stable managed-switch architecture rather than an unmanaged distribution block, with network services controlled through the selected catalog configuration.

The common Device Level Ring capability supports ring-based industrial network design. The difference is functional scope: 1783-CMS20DN adds Parallel Redundancy Protocol and Network Address Translation, while 1783-CMS20DP remains the DLR managed-switch variant. A design that uses PRP or NAT therefore requires the DN model to remain explicit in the configuration record.

Technical Specifications

Specification 1783-CMS20DP / 1783-CMS20DN
Brand Allen-Bradley
Product family Stratix 5200 managed Ethernet switches
Models covered 1783-CMS20DP / 1783-CMS20DN
Total ports 20
Copper interfaces 18 x 10/100/1000Base-T
Dual-purpose positions 2; RJ45 or approved SFP, one active interface per position
Switching capability Managed; Device Level Ring
1783-CMS20DP distinction DLR managed switch
1783-CMS20DN distinction DLR, PRP and NAT
Power input 12...48 V DC nominal; 4.2 A maximum
Power consumption 36.7 W
Alarm relay 30 V DC, 1 A or 60 V DC, 0.5 A resistive
Mounting Vertical DIN rail
Operating temperature -40 to 60 °C (-40 to 140 °F)
Enclosure type Open-style

Cabinet wiring and alarm preparation

System focus

Cabinet wiring and alarm preparation

Before a CMS20DP or CMS20DN is energized, mount it vertically on the DIN rail, bond the designated ground connection, and route the 12...48 V DC supply separately from noisy field conductors. The installation instructions also reserve the front-panel power and alarm connectors for accessible service, rather than allowing cable dressing to block them.

The switch provides two alarm inputs and one Form C alarm-output relay. A commissioning record should identify which external circuit uses IN1/IN2 and which contact uses the N.O., N.C. or COM relay path, so an alarm issue is not mistaken for a network-port fault.

  • 12...48 V DC nominal supply
  • Two inputs + one Form C alarm output
  • Vertical DIN-rail installation

Dual-purpose port and SFP discipline

Technical reference

Dual-purpose port and SFP discipline

Each dual-purpose position combines an RJ45 interface and an approved SFP location, but only one interface may be active at a time. The copper-versus-fiber choice must therefore be recorded for both positions before the cable schedule and SFP order are released.

After an SFP connection is made, the port can show amber while the device discovers topology and checks for loops; the instruction gives approximately 30 seconds before normal green link status. This observed startup state should not be escalated as a hardware failure prematurely.

  • 18 fixed copper ports
  • 2 RJ45-or-SFP positions
  • Allow topology discovery before faulting

Frequently Asked Questions

In a DLR plant expansion, why must the drawing name 1783-CMS20DP / 1783-CMS20DN exactly?

Both 1783-CMS20DP and 1783-CMS20DN provide DLR, but 1783-CMS20DN also lists PRP and NAT. The catalog suffix therefore identifies a network-service boundary, not a cosmetic revision.

When an existing cabinet calls for 20 connections, which 1783-CMS20DP / 1783-CMS20DN ports need separate planning?

1783-CMS20DP and 1783-CMS20DN have eighteen copper 100/1000 ports plus two 100/1000 combo ports. The combo positions must be assigned as the intended connection type rather than counted as identical copper-only ports.

How should a control engineer avoid a NAT feature gap with 1783-CMS20DP / 1783-CMS20DN?

The NAT requirement must be matched to 1783-CMS20DN because that feature is listed for the DN model. 1783-CMS20DP should not be substituted on the basis of the shared DLR and port-count description.

What enclosure review is needed before fitting 1783-CMS20DP / 1783-CMS20DN near process heat?

1783-CMS20DP and 1783-CMS20DN are specified for an IP30 environment and -40 to 60 °C operation. The enclosure and its thermal condition must support those values before the switches are energized.

During a migration, what remains common between 1783-CMS20DP / 1783-CMS20DN?

1783-CMS20DP and 1783-CMS20DN share a Stratix 5200 managed-switch role, eighteen copper ports, two combo ports, and DLR capability. The selection changes when PRP or NAT is part of the documented network need.

Which mounting assumption is safe for 1783-CMS20DP / 1783-CMS20DN?

Both 1783-CMS20DP and 1783-CMS20DN are listed for DIN-rail mounting. The rail installation does not remove the need to maintain the specified IP30 cabinet environment.

Moore Automation

Moore Automation

Application enquiry review

For a managed-network enquiry, Moore Automation can begin with the exact switch suffix, port plan and intended network services. This keeps a request for DLR, PRP or NAT aligned to the catalog number supplied.

  • Original products
  • Fast delivery
  • 1-year warranty
  • 12-hour online response

Contact Moore Automation

Manager

Leonia

No related record found

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.