AC supply path
PW481-51 receives 100–120 V AC through the host power connection. Its 50/60 Hz input is the AC branch used when the cabinet distributes mains power to the FCU, FIO unit or optical repeater.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Yokogawa PW481-51 / PW484-50 Input Power Supply Modules |
| Item NO. | 2932312 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | YOKOGAWA |
| Brand | YOKOGAWA |
| Creation Time | 2026-11-13 |
Yokogawa PW481-51 / PW484-50 are exclusive input power supply modules for CENTUM VP field control units, field I/O units and optical ESB bus repeater modules. Each converts the specified site supply into the internal power required by its host unit; PW481-51 accepts an AC source, while PW484-50 accepts a 24 V DC source.
Within an FCU or I/O unit, PW481-51 / PW484-50 occupy the dedicated P1 or P2 power-module position rather than a signal-I/O slot. A single-power arrangement uses P1, whereas a dual-redundant arrangement requires two units of the same model so that the AC and DC variants are not combined in one pair.
The order codes PW481-51 / PW484-50 also distinguish environmental construction. Both codes specify no explosion-protection option and G3 coating; the remaining selection difference is the incoming supply, which must be matched to the cabinet power distribution before the module is assigned.
| Specification | PW481-51 | PW484-50 |
|---|---|---|
| Brand | Yokogawa | |
| Product type | AC input power supply module | DC input power supply module |
| Host equipment | FCU, FIO unit or optical ESB repeater | |
| Rated input | 100–120 V AC ±10% | 24 V DC ±10% |
| Input frequency | 50/60 Hz ±3 Hz | Not applicable |
| Maximum consumption | 200 VA | 5.5 A |
| Power-module position | P1 or P2 | |
| Redundant arrangement | Two identical PW481 units | Two identical PW484 units |
| External connector | Exclusive module connector | |
| Dimensions | 49.7 × 149 × 199.5 mm | |
| Approximate weight | 1.0 kg | |
| Explosion protection | None | |
| Coating | G3 | |
| Operating range code | −20 to 70 °C construction | |
| Order-code suffix | -51 | -50 |
PW481-51 / PW484-50 separate the incoming-power choice from the host unit’s internal distribution. The three relationships below show where each variant enters the unit and how a redundant pair is formed.
PW481-51 receives 100–120 V AC through the host power connection. Its 50/60 Hz input is the AC branch used when the cabinet distributes mains power to the FCU, FIO unit or optical repeater.
PW484-50 receives a nominal 24 V DC feed. The DC source is selected at the cabinet level, while the exclusive module connector carries the converted power into the host unit.
PW481-51 / PW484-50 install in the dedicated P1/P2 area. P1 is used for a single module; P1 and P2 are populated with two identical units when redundant power is required.
The PW481-51 / PW484-50 suffixes define more than a label: they preserve the supply and construction choices that must stay consistent with the host unit and with the second power module.
A redundant PW481-51 / PW484-50 arrangement is model-homogeneous. Two PW481-51 units form the AC pair, or two PW484-50 units form the DC pair.
PW481-51 / PW484-50 carry the no-explosion-protection selection and G3 coating. These suffix positions should remain visible when matching an installed module.
PW481-51 / PW484-50 share the same 49.7 × 149 × 199.5 mm envelope and approximate 1.0 kg mass, so supply type—not the outline—distinguishes the two variants.
No. PW481-51 / PW484-50 identify different incoming supplies. A redundant installation uses two identical PW481-51 units for AC or two identical PW484-50 units for 24 V DC.
A single PW481-51 / PW484-50 module is assigned to the P1 power position. P2 is used when the host unit is equipped with the second identical module.
Confirm whether the cabinet delivers 100–120 V AC or 24 V DC. PW481-51 / PW484-50 share an outline but do not share an input specification.
No. PW481-51 / PW484-50 are exclusive host-unit power modules and occupy the designated P1/P2 power locations, not a signal-module slot.
For PW481-51 / PW484-50, the supplied suffixes preserve the construction selection: both are no-explosion-protection versions with G3 coating, while the base model distinguishes AC from DC input.
A PW481-51 / PW484-50 enquiry should state the exact installed code, host unit, P1/P2 arrangement, incoming supply and quantity so the AC/DC and redundant-pair boundaries remain explicit.
https://www.mvme.cn
Moore Automation handles enquiries across established control, drive, turbine-control and condition-monitoring families. Requests are recorded by brand, complete model and required quantity before product information is compared.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found