Eight input loops
AAI841-H50 receives eight 4–20 mA signals. Two-wire transmitters can use the module’s transmitter-supply path, while four-wire devices provide their own field power and return only the measured current.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Yokogawa AAI841-H50 Analog I/O Module |
| Item NO. | 2932314 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | YOKOGAWA |
| Brand | YOKOGAWA |
| Creation Time | 2026-11-13 |
Yokogawa AAI841-H50 is a non-isolated analog input/output module for CENTUM VP field I/O. It combines eight 4–20 mA input channels and eight 4–20 mA output channels in one module, placing field-current acquisition and controller-driven current output in the same FIO position.
On AAI841-H50, each input channel accepts either a two-wire transmitter loop or a four-wire current signal through its assigned pins. The module converts those currents for the control station while the output half converts controller values back into current loops; channel wiring therefore determines whether transmitter power and signal return share the module path.
AAI841-H50 adds HART digital communication to the analog current path. HART data is superimposed on the 4–20 mA loop, and Command 3 process variables can be handled without replacing the analog measurement; the H suffix identifies this communication function, while -50 specifies the basic, non-explosion-protected construction.
| Specification | Specification details |
|---|---|
| Brand | Yokogawa |
| Model | AAI841-H50 |
| Product type | Analog input/output module |
| Country | Not specified |
| Analog inputs | 8 channels, 4–20 mA |
| Analog outputs | 8 channels, 4–20 mA |
| Channel isolation | Non-isolated |
| Digital communication | HART |
| Input accuracy | ±16 µA |
| Output accuracy | ±48 µA |
| Data update period | 10 ms |
| Output load | 0–750 Ω; 200–750 Ω at 60–70 °C |
| Transmitter supply | At least 14.8 V at 20 mA |
| External connection | Pressure clamp, KS cable or MIL connector |
| Approximate weight | 0.30 kg |
AAI841-H50 divides its sixteen analog points between acquisition and actuation. The current path changes direction across the two channel groups, while HART communication remains coupled to the same field loops.
AAI841-H50 receives eight 4–20 mA signals. Two-wire transmitters can use the module’s transmitter-supply path, while four-wire devices provide their own field power and return only the measured current.
AAI841-H50 drives eight 4–20 mA output circuits. The connected load must stay within the specified resistance range so the commanded current can be established across the field loop.
AAI841-H50 carries HART digital information over the analog current. Command 3 variables travel through the HART channel while the continuous 4–20 mA value remains available to the controller.
AAI841-H50 depends on the selected terminal interface and on loop conditions at each channel. These boundaries connect the module’s published accuracy and diagnostic behavior to actual field wiring.
AAI841-H50 can connect through a pressure-clamp terminal block, a KS cable interface or a MIL-style connector arrangement. The selected interface must preserve the input/output pin assignment.
AAI841-H50 detects an open output circuit when the output current falls below 0.65 mA. This indication concerns the output loop and is separate from an input-channel reading.
AAI841-H50 permits a 0–750 Ω output load through most of its range; at 60–70 °C the lower bound becomes 200 Ω. The load check therefore belongs to the output loop and ambient condition together.
For AAI841-H50, a two-wire transmitter uses the module supply and signal path, while a four-wire transmitter has an external supply and sends its current into the designated input pins.
No. AAI841-H50 has eight receiving channels and eight driving channels. Their current direction, terminal pins, accuracy figures and diagnostics are different.
For AAI841-H50, verify the output-loop continuity and whether current is below the 0.65 mA detection threshold, then confirm that the connected load is within the permitted range.
AAI841-H50 includes HART communication in the analog I/O module. The field loop still carries 4–20 mA, with HART data superimposed on that current path.
AAI841-H50 supports documented pressure-clamp, KS-cable and MIL-connector arrangements. The selected terminal or cable must match the channel pin assignment.
State AAI841-H50 in full and include the terminal interface, input transmitter type, output-load range and HART requirement. This separates the exact HART version from related analog modules.
https://www.mvme.cn
Moore Automation keeps the manufacturer, full order code, quantity and destination together in one enquiry record. Datasheet checks and commercial communication then refer to the same identifier.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found