Triconex 3720 | 64-point TMR single-ended analog input module

Triconex 3720 | 64-point TMR single-ended analog input module Item NO.: 2918959

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name Triconex 3720 | 64-point TMR single-ended analog input module
Item NO. 2918959
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category TRICONEX
Brand TRICONEX
Creation Time 2026-10-13

Triconex 3720 | 64-point TMR single-ended analog input module

Triconex safety-system hardware

Triconex 3720 | 64-point TMR single-ended analog input module

64-point TMR single-ended analog input module · Tricon v10.2 and later systems · exact-model selection

01

Product Details

Built for Tricon v10.2 and later systems, the Triconex 3720 is a 64-point TMR single-ended analog input module. It converts 0–5 VDC field signals into triplicated process values, giving the controller a high-density input bank with programmable 12-bit or 14-bit resolution.

With Triconex 3720, each of the 64 field inputs is referenced to its assigned return rather than paired with a second signal lead. The single-ended values are sampled at a 10 ms update rate, and the conversion can be set to 12-bit or 14-bit resolution before the triplicated data is delivered to the controller.

The field side of Triconex 3720 is separated from the system side by a specified 800 VDC minimum isolation. A 0–20 mA signal can use a 250 Ω shunt, while the separate Field indicator works alongside Pass, Fault, and Active to show field and module status.

02

Specifications Overview

Technical Item 3720
Brand Triconex
Product Type TMR single-ended analog input
System Tricon v10.2 and later
Input Points 64 single-ended
Input Range 0–5 VDC
Input Update Rate 10 ms
Resolution 12 or 14 bits, programmable
Accuracy Less than 0.15% of FSR, 0–60 °C
Input Resistance 10 MΩ minimum
Channel Isolation 420 kΩ typical
Field-to-System Isolation 800 VDC minimum
Current Conversion 0–20 mA plus 6% over-range with 250 Ω shunt
Over-range Protection 150 VDC or 115 VAC continuous
Logic Power Less than 12 W
Indicators Pass, Fault, Active, Field
03

Operating Characteristics

Triconex 3720 uses a single-ended 64-point layout and a 10 ms sample period, which keeps the channel organization different from the 32-point differential input family.

01

Single-ended channels

Each of the 64 inputs uses its field return arrangement instead of a differential pair.

02

Programmable resolution

The input conversion can be configured for 12-bit or 14-bit resolution.

03

Fast update path

The 10 ms input update rate links the field sample to the controller data image.

04

System Integration

Triconex 3720 belongs in the later Tricon platform versions and keeps field-side wiring separated from the controller-side bus.

01

Version boundary

The module is specified for Tricon v10.2 and later systems.

02

Low-density compatibility

A low-density chassis must already be upgraded to v10.2.x or later before this module is fitted.

03

Isolation path

The field input side has 800 VDC minimum isolation from the system side.

05

Product Q&A

Why are the 64 Triconex 3720 inputs called single-ended?

For Triconex 3720, Each input is measured against its assigned return instead of being paired with a second signal lead. That wiring organization is different from a differential analog input bank.

What does the programmable resolution change in Triconex 3720?

Triconex 3720 can present the converted value at either 12-bit or 14-bit resolution. The choice affects the digital representation of the 0–5 V input, not the number of field channels.

How is a 0–20 mA signal connected to Triconex 3720?

For Triconex 3720, A 250 Ω shunt converts the current into the voltage seen by the input circuit, with the specified 6% over-range allowance. The module remains a 64-point single-ended input device.

Which chassis version is required for Triconex 3720?

Triconex 3720 is specified for Tricon v10.2 and later systems. A low-density chassis must already be upgraded to v10.2.x or later for this module arrangement.

How do the two isolation figures apply to Triconex 3720?

For Triconex 3720, The 800 VDC minimum value describes field-to-system isolation, while 420 kΩ typical describes channel isolation. They refer to different parts of the input structure.

How does the Field indicator differ from Pass and Fault in Triconex 3720?

For Triconex 3720, The Field indicator identifies the field-side condition separately from Pass, Fault, and Active module indicators. This lets the input wiring state be read apart from the module-level state.

06

Why Choose Moore Automation

Moore Automation

https://www.mvme.cn/

Moore Automation keeps the information needed for a parts enquiry together so the requested item is not separated from its quantity or destination.

Clear requestThe model and quantity remain visible as one record.
Direct contactThe page shows a named manager and direct channels.
Follow-up continuitySubsequent communication refers back to the same request.
www.mvme.cn

No related record found

You May Also Like

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.