HE800ACM200 is a SmartStack AC power-monitoring module for three-phase voltage and current measurement. It accepts a 120 V three-phase wye voltage input and three 5 A current inputs through external potential and current transformers.
The module reports voltage, current, phase and frequency values to the controller. Its mapped analog-input registers also support calculated quantities such as per-phase volt-amperes, total watts and power factor within the controller application.
| Technical Item | Specification Value |
|---|---|
| Brand | Horner |
| Model | HE800ACM200 |
| Product Type | SmartStack AC power monitor |
| Brand Country | United States |
| Voltage Input | 120 V three-phase wye; 208 V line-to-line |
| Voltage Input Impedance | 1 MΩ to ground |
| Current Input | Three-phase, 5 A |
| Input Frequency | 50–70 Hz |
| Voltage Accuracy / Resolution | 0.2% / 0.1 V |
| Current Accuracy / Resolution | 0.2% / 0.005 A |
| Frequency Accuracy / Resolution | 0.1% / 0.01 Hz |
| Phase Accuracy / Resolution | 0.2° / 0.1° |
| Power | 1.5 W; 60 mA at 24 VDC |
| Operating Temperature | 0–60°C |
| Relative Humidity | 5–95%, non-condensing |
| Weight | 9 oz (256 g) |
The mapped values cover three phase voltages, three phase currents, differential phase, individual phase angles and line frequency. Voltage and current values update once per PLC scan; frequency and phase values update once per line cycle.
Controller logic can combine these registers to calculate volt-amperes, watts, power factor, VAR and accumulated energy. The calculations use the documented scaling and phase relationships rather than values generated inside the module.
External PTs are required for voltage inputs and external CTs for the 5 A current inputs. Each CT low input returns to current-sense common, either directly or through a suitable monitoring switch arrangement.
The wiring figure shows both CT return methods and the three-phase voltage terminals. Open it before assigning the eleven front terminals.
No. The documented input is 120 V three-phase wye, 208 V line-to-line, and external potential transformers are required.
Use external 5 A CTs and return each CT low side to common directly or through a suitable monitoring switch arrangement.
The L1 voltage channel is the reference for phase and frequency measurements.
The manual provides controller formulas; application logic accumulates the calculated watt value over time.
Check module order because differential phase is reported relative to an adjacent unit, with a defined wrap relationship when four monitor modules are stacked.
Moore Automation supplies automation components across multiple established brands and product families. The company focuses on identified model requests, fast delivery and 100% original products backed by a 12-month warranty.
Send the complete catalog number and required quantity for product identification and order assistance.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found