Copy| Product Name | GE Fanuc IC695ALG708-AB RX3i 8-Channel Non-Isolated Analog Output Module |
| Item NO. | 2944929 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-25 |
Complete catalog identity · manual-supported facts · product-specific configuration
GE Fanuc IC695ALG708-AB is the AB release of the PACSystems RX3i eight-channel non-isolated current/voltage output module. It converts controller output data into individually enabled analog signals and reports channel, terminal-block and module conditions to the RX3i CPU.
Each channel of GE Fanuc IC695ALG708-AB can be configured for 0–20 mA, 4–20 mA, 0–10 V or ±10 V service. Scaling, offset, alarm limits, clamping and fallback behavior are set in software, while the external 24 VDC source is connected directly at the terminal block.
Release history associates GE Fanuc IC695ALG708-AB with firmware 1.08 and upgrade kit 44A753282-G01. The module belongs in an RX3i Universal Backplane and requires a supported RX3i CPU and Machine Edition environment for configuration.
GE Fanuc IC695ALG708-AB gives each channel a configured response when normal output control is interrupted.
A channel can retain its last commanded value while field power and module operation remain available.
The project can assign a default output or bias value that the channel uses under the selected fault condition.
High/low limits, clamping and latching diagnostics keep the commanded word inside the configured channel behavior.
The removable terminal assembly is part of the field boundary for GE Fanuc IC695ALG708-AB.
Box and spring terminal blocks are supported, with extended versions providing additional depth for shielded wiring.
The TB status circuit tells the module whether the terminal block is installed; it does not prove every field conductor is correct.
The external source connects directly to the module terminal block and cannot be supplied through the universal-backplane TB1 connection.
Command a controlled value on GE Fanuc IC695ALG708-AB and measure at the terminal block with a known load. Compare the raw command, channel status, field voltage and loop continuity.
No. GE Fanuc IC695ALG708-AB requires external 24 VDC connected directly to its terminal block; the universal-backplane TB1 path is not used for this module.
GE Fanuc IC695ALG708-AB can be configured to hold last state, use a default or apply a bias. Review the channel fault-action settings before treating the fixed value as a hardware failure.
GE Fanuc IC695ALG708-AB is associated with firmware 1.08 and upgrade kit 44A753282-G01. Preserve both the AB suffix and installed firmware when comparing later revisions.
Verify that the supported block is fully seated on GE Fanuc IC695ALG708-AB and that its actuator reaches the detector. The TB indication does not evaluate individual wire continuity.
Export the GE Fanuc IC695ALG708-AB hardware configuration, channel ranges, scaling, alarm and clamp limits, fallback values, terminal-block type, firmware and field-power wiring.
Moore Automation keeps model, document, packing and shipment information together under one managed record. This reduces identity drift when a request includes hardware suffixes, terminal accessories or legacy control-system parts.