Loop entry
Each transmitter current crosses a 250 Ω input path assigned to one channel; the external supply must also furnish the loop current.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC694ALG223-GL RX3i 16-Channel Current Input Module |
| Item NO. | 2944918 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-25 |
Complete catalog identity · manual-supported facts · product-specific configuration
GE Fanuc IC694ALG223-GL is the GL-revision identity of the PACSystems RX3i IC694ALG223 high-density analog current input module. It converts sixteen single-ended field-current loops into controller input words and reports module and external-supply status through the RX3i backplane.
Each channel of GE Fanuc IC694ALG223-GL can be configured for 0–20 mA, 4–20 mA, or 4–20 mA Enhanced operation. The enhanced range extends low-current measurement toward 0 mA so an open circuit can be separated from a valid 4 mA process value when the alarm limits are configured for that purpose.
Logic for GE Fanuc IC694ALG223-GL is powered from the 5 V backplane bus, while the current-loop side needs a user 24 VDC source. The two front indicators therefore distinguish module execution from field-supply availability instead of presenting one combined power state.
GE Fanuc IC694ALG223-GL keeps field-loop power, conversion and controller data as separate stages.
Each transmitter current crosses a 250 Ω input path assigned to one channel; the external supply must also furnish the loop current.
The selected range controls how measured current is represented in the input word. All sixteen conversions are refreshed as one module cycle.
The completed words and diagnostic bits are transferred to the configured RX3i input references for application use.
The enhanced range of GE Fanuc IC694ALG223-GL gives low-current alarms a defined diagnostic purpose.
A valid 4–20 mA signal is scaled inside the configured process range rather than treated as a raw voltage.
In Enhanced mode the conversion remains active below 4 mA, allowing a low alarm to identify current moving toward an open circuit.
Module OK reports execution and configuration state, while User Supply reports the external 24 VDC condition.
GE Fanuc IC694ALG223-GL receives logic power from the backplane but needs a separate user 24 VDC source for the loop side. Check the User Supply indicator and measure the field source before changing channel configuration.
Put the affected GE Fanuc IC694ALG223-GL channel in 4–20 mA Enhanced mode and review the low-alarm threshold, loop supply, terminal torque and transmitter continuity. The extended low-current region is what distinguishes a broken loop from a valid 4 mA reading.
GE Fanuc IC694ALG223-GL completes one all-channel conversion cycle in about 13 ms. Compare the controller scan and filtering with that module cycle instead of expecting independent per-channel scan times.
Record the complete GE Fanuc IC694ALG223-GL suffix, channel range and scaling, alarm limits, terminal assignments, loop-power arrangement and slot configuration. Those items determine whether the new hardware will produce the same controller data.
The IC694ALG223 family supports hot insertion from revision BA onward, so the GL-marked GE Fanuc IC694ALG223-GL is later than that boundary. Follow the documented hot-insertion procedure and do not disturb live field wiring outside the approved process.
Inject a known current at the GE Fanuc IC694ALG223-GL terminal and compare the raw input word with the configured range. A correct injected value points to the transmitter or loop wiring; a wrong value keeps the channel configuration and module path in scope.
Moore Automation keeps each customer record tied to the manufacturer, complete catalog suffix, quantity and destination. Document questions and order communication remain connected to the same record so revision details do not become detached from the request.