Shared group
Fifteen single-ended inputs use the module common structure defined by the terminal drawing.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC200ALG265D / IC200ALG265G 15-Channel Voltage Analog Input Modules |
| Item NO. | 2945589 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-11-27 |
GE Fanuc IC200ALG265D and IC200ALG265G are revision-labelled executions of the VersaMax IC200ALG265 fifteen-channel voltage analogue input module. The module receives fifteen single-ended voltage signals in one common group and converts them into 15-bit controller data.
All enabled inputs on IC200ALG265D and IC200ALG265G are scanned through the same conversion path. Each channel is compared with the configured operating limits, while the module performs an internal conversion check that can place the module into a fault condition when repeated conversion errors are detected.
Field conductors for IC200ALG265D and IC200ALG265G land on the carrier terminal rows identified in the wiring diagram. The shared common arrangement makes the source reference and grounding plan part of the channel organization rather than an independent return for every input.
The channels share one module conversion cycle while remaining distinct in the controller input map.
Fifteen single-ended inputs use the module common structure defined by the terminal drawing.
The conversion path samples the enabled channels and completes one module update in the published cycle.
Each voltage is represented by a 15-bit value with the defined voltage-per-count relationship.
The completed values are placed in consecutive analogue input references for the configured module.
One shared conversion path updates the channel set, but each result retains its own terminal and controller reference. This relationship lets a technician compare a field test point with the corresponding input word without treating the module as one combined measurement.
Field reference quality and internal conversion checks determine whether a channel value can be trusted.
Every voltage source must share the common arrangement shown for the carrier terminals.
Input protection withstands the specified fault voltage but does not replace correct source limiting.
The module applies an internal reference to detect repeated A/D conversion errors.
Repeated internal errors extinguish the OK indication and report the fault to the CPU or NIU.
Because the inputs share the common structure, a reference or bonding problem can influence several readings at once. The internal conversion check addresses a different boundary, allowing common wiring faults and module conversion faults to be investigated separately.
Use the complete label and keep D and G on separate line items. Their base channel behavior follows IC200ALG265, but the revision letter remains part of the exact supplied identity.
Because the channels share a common reference, inspect the module common, source references and cabinet bonding before treating each channel as an independent transmitter fault.
Read the CPU or NIU diagnostics and verify supply and carrier seating. Repeated internal conversion-check failures can place the module in fault and may require a controlled power cycle or replacement.
Not as a current input. IC200ALG265D measures voltage; a current loop requires the correct current-input module or an approved external conversion arrangement.
Apply traceable negative, zero and positive voltage points to each used channel while monitoring the corresponding controller reference and diagnostic state.
Retain the exact revision label, carrier position, terminal map, common wiring, controller references and any application scaling.
Moore Automation keeps D and G revision labels on separate enquiry rows and records the carrier and channel requirement for each request.
Quotation information, requested documents and shipment communication remain attached to the selected revision.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found