Translate field voltage into logic
VE4001S2T1B1 evaluates each isolated field circuit and reports its state through the DeltaV I/O path. Channel isolation prevents one field loop from becoming the shared electrical reference for the others.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Emerson DeltaV VE4001S2T1B1 / VE4002S1T1B1 Isolated Discrete I/O Assemblies |
| Item NO. | 2940700 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | EMERSON |
| Brand | EMERSON |
| Creation Time | 2026-11-18 |
An isolated 24 V DC input assembly paired with an isolated 24 V DC output assembly.
Emerson DeltaV VE4001S2T1B1 / VE4002S1T1B1 are eight-channel isolated discrete I/O assemblies for M-series traditional I/O. VE4001S2T1B1 reads 24 V DC field states; VE4002S1T1B1 switches 24 V DC loads through independently isolated output channels.
The VE4001S2T1B1 input path recognizes an on state above 10 V DC and an off state below 5 V DC. The VE4002S1T1B1 output path operates across 2 to 60 V DC and supports discrete, momentary and continuous-pulse channel behavior.
The two assemblies use opposite signal paths. VE4001S2T1B1 converts eight externally powered field states into LocalBus input data, whereas VE4002S1T1B1 converts controller commands into eight isolated load-driving outputs with discrete and timed operating modes.
| Specification | VE4001S2T1B1 | VE4002S1T1B1 |
|---|---|---|
| Brand | Emerson DeltaV | Emerson DeltaV |
| Assembly type | 8-channel isolated discrete input | 8-channel isolated discrete output |
| Nominal field class | 24 V DC input | 24 V DC output |
| Channel count | 8 | 8 |
| Isolation | Channel-to-system and channel-to-channel; 1500 V DC factory test | Channel-to-system and channel-to-channel; 1500 V DC factory test |
| On / operating threshold | On above 10 V DC | Output range 2 to 60 V DC |
| Off / leakage | Off below 5 V DC | 1.2 mA maximum off-state leakage |
| Channel load | 5 mA at 24 V input | 1.0 A output rating |
| LocalBus current | 75 mA typical; 100 mA maximum | 100 mA typical; 150 mA maximum |
| Field circuit power | None | None |
| Channel modes | Discrete input | Discrete, momentary or continuous pulse |
| Termination | Standard I/O termination block | Standard I/O termination block |
| Optional fuse | 2.0 A | Managed by the selected termination arrangement |
The two assemblies form opposite sides of a discrete control loop and retain separate input and output identities.
VE4001S2T1B1 evaluates each isolated field circuit and reports its state through the DeltaV I/O path. Channel isolation prevents one field loop from becoming the shared electrical reference for the others.
VE4002S1T1B1 receives controller output states and switches the corresponding isolated field channels. Its timed modes extend the same hardware path to momentary and repeating-pulse behavior.
An input channel observes an externally created state, while an output channel creates a controlled state at the load. This directional distinction governs the wiring, database tag and diagnostic path.
Isolation limits fault propagation, while practical diagnosis still depends on field-voltage and termination checks.
A VE4001S2T1B1 symptom can originate at the field source, terminal, isolated channel or controller database. The on/off threshold separates an indeterminate field voltage from a valid logic state.
A VE4002S1T1B1 channel combines controller logic, output electronics, field supply and the connected load. Observing those points separately distinguishes a control-state problem from a power-path problem.
Channel-to-channel isolation limits the electrical coupling between loops. The standard termination path still preserves a fixed relationship between each field terminal and its card channel.
Moore Automation structures discrete-I/O enquiries around the loop rather than the part number alone. The team can keep card identity, termination type, channel direction, field voltage and destination information together for quotation and receiving review.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found