Welcome to Moore Automation Limited

0
Loadding...
 

sales@mvme.cn    Phone: +86 18030175807

Home>EMERSON>Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block
Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block

Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block Item NO.: 2945609

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block
Item NO. 2945609
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category EMERSON
Brand EMERSON
Creation Time 2026-11-27

Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block | Moore Automation
EMERSON
INDUSTRIAL · CONTROL
DeltaV SIS SLS Redundant Terminal Block

Emerson 12P3323X053 DeltaV SIS SLS Redundant Terminal Block

KJ2201X1-JA1 terminal hardware for redundant DeltaV SIS logic-solver field connections

01 / Product

Product Presentation

Redundant field termination for a DeltaV SIS logic-solver channel is the role of Emerson 12P3323X053. The assembly is associated with KJ2201X1-JA1 SLS redundant terminal-block hardware and provides the defined field-wiring boundary between redundant logic-solver electronics and the connected safety circuit.

Two documented circuit paths distinguish 12P3323X053: the A-B path is limited to 30 mA per channel, while the A-C path permits up to 1 A per channel at a 30 VDC maximum input. Those terminals are not interchangeable labels; each represents a different approved electrical route through the terminal block.

Environmental construction for 12P3323X053 covers -40 to +70 deg C operation, 5-95% non-condensing humidity, G3 airborne-contaminant service, specified vibration and 10 g shock. The terminal block contains no field-serviceable parts and requires no calibration.

02 / Data

Engineering Specifications

Technical Item 12P3323X053
Brand Emerson
Product Type DeltaV SIS SLS redundant terminal block
Brand Country United States
Associated Hardware Model KJ2201X1-JA1
Maximum Input Voltage 30 VDC
A-B Circuit Limit 30 mA per channel
A-C Circuit Limit 1 A per channel
Operating Temperature -40 to +70 deg C
Relative Humidity 5-95%, non-condensing
Airborne Contaminants ISA-S71.04 G3
Shock 10 g, 11 ms
Low-Frequency Vibration 1 mm peak-to-peak from 2 to 13.2 Hz
High-Frequency Vibration 0.7 g from 13.2 to 150 Hz
Service Requirements No calibration; no field-serviceable parts
03 / Safety Path

Redundant SLS Termination Boundaries

Defined field interface

The terminal block keeps the field circuit at the documented redundant logic-solver boundary.

12P3323X053 is not a general-purpose marshalling strip. Its associated KJ2201X1-JA1 hardware is assigned to the SLS redundant terminal position, so terminal identity, channel wiring and the mating carrier location remain part of one safety-system installation record.

A

Channel identity

Field conductors on 12P3323X053 retain the channel position used by the redundant SLS hardware instead of being regrouped as an ordinary terminal bank.

B

Powered handling

12P3323X053 is not inserted, removed or rewired while energized; site procedures first isolate the associated field and system power.

04 / Electrical Routes

A-B and A-C Circuit Paths

A-B path

The A-B route through 12P3323X053 is documented for a maximum of 30 mA per channel at up to 30 VDC.

A-C path

The A-C route through 12P3323X053 supports up to 1 A per channel at the same 30 VDC maximum input boundary.

Terminal discipline

Circuit drawings for 12P3323X053 must identify whether each load uses A-B or A-C; the higher current figure cannot be applied to both paths.

05 / Answers

Support Questions

Why must the A-B and A-C paths on 12P3323X053 be checked separately?

12P3323X053 assigns different current limits to the two paths: 30 mA per channel for A-B and 1 A per channel for A-C. Using the A-C limit for an A-B circuit would exceed the documented terminal-block boundary.

Can 12P3323X053 be removed while its DeltaV SIS carrier is energized?

No. 12P3323X053 must not be inserted, removed or rewired while powered. The associated system and field sources are isolated before the terminal block or its conductors are handled.

Does 12P3323X053 require a calibration interval?

12P3323X053 is passive terminal hardware and has no calibration requirement. Functional proof testing belongs to the complete safety loop rather than an adjustment inside the terminal block.

Which environmental class applies to 12P3323X053 in a control cabinet?

12P3323X053 is documented for ISA-S71.04 G3 airborne contaminants, -40 to +70 deg C and 5-95% non-condensing humidity. The surrounding enclosure still has to maintain those conditions.

What should be inspected after a vibration event involving 12P3323X053?

For 12P3323X053, check terminal tightness, connector seating, channel labeling and the redundant SLS mating position before returning the loop to service. The documented vibration limits do not replace a physical inspection after abnormal cabinet movement.

Why should the full 12P3323X053 identity stay with KJ2201X1-JA1 records?

12P3323X053 identifies the supplied terminal-block record, while KJ2201X1-JA1 identifies the associated hardware model. Keeping both references together prevents a similar DeltaV terminal assembly from being treated as the same SLS redundant interface.

06 / Moore

Safety-System Record Control

www.mvme.cn

Moore Automation

https://www.mvme.cn/

Moore Automation maintains complete hardware, terminal and destination records for Emerson 12P3323X053. Careful identity review, document coordination and traceable communication keep the terminal-block record and its carrier assignment visible as one safety-system component record.

Record continuityPart and hardware identity paired
Document controlAvailable safety records aligned
Communication chainOne assigned contact path
08 / Contact

Sales & Support

Moore AutomationSales & Support
ManagerLeonia

No related record found

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.