Pepperl+Fuchs FS-LBF-I1.32 Fieldbus Surge Protector
Intrinsically safe M20 threaded transient protector for FOUNDATION Fieldbus H1 and PROFIBUS PA
Model Summary
Transient energy on an intrinsically safe fieldbus spur is diverted to earth by Pepperl+Fuchs FS-LBF-I1.32. The stainless-steel threaded protector covers both the positive and negative fieldbus leads with gas-discharge protection while the green-yellow conductor provides the earth path.
Field protocols remain transparent through FS-LBF-I1.32. Its 32 VDC rating, FISCO and Entity compatibility, and IEC 61158-2 application make the protector suitable for FOUNDATION Fieldbus H1 and PROFIBUS PA segments without converting or separating the communication signal.
Mechanical identity on FS-LBF-I1.32 combines an M20 x 1.5 threaded housing, IP67 enclosure protection and intrinsically safe Ex ia construction for Zone 1 installation. The device is installed in the threaded cable entry of the field housing and relies on a short, low-impedance earth connection.
Technical Reference
| Technical Item | FS-LBF-I1.32 |
|---|---|
| Brand | Pepperl+Fuchs |
| Product Type | Fieldbus surge protector |
| Brand Country | Germany |
| Fieldbus Standards | FOUNDATION Fieldbus H1 and PROFIBUS PA |
| Intrinsic-Safety Concepts | FISCO or Entity |
| Rated Voltage | 32 VDC |
| Rated Current | 550 mA |
| Nominal Discharge Current | 10 kA per line; 10 kA total |
| Maximum Surge Current | 10 kA, 8/20 microsecond waveform |
| Protection Level Line-to-Line | 58 V at maximum rated current |
| Protection Level Line-to-Earth | 1700 V at maximum rated current |
| Housing / Thread | Stainless steel; M20 x 1.5 |
| Ingress Protection | IP67 |
| Hazardous-Area Use | Intrinsically safe Ex ia, Zone 1 |
Transient Diversion at the Fieldbus Spur
Both signal conductors are clamped while surge current is directed toward earth.
FS-LBF-I1.32 connects red and black fieldbus conductors through the surge network and bonds the protective branch to the green-yellow earth lead. Gas-discharge elements carry high transient energy away from the connected field device and control interface.
Protocol-transparent path
FS-LBF-I1.32 does not regenerate or interpret the IEC 61158-2 signal; it remains a protective element in the existing fieldbus segment.
Coordinated protection
Effective use of FS-LBF-I1.32 depends on a lightning-protection-zone concept and an earth route short enough to avoid adding excessive inductive voltage.
Threaded Installation and Intrinsic-Safety Boundary
The M20 x 1.5 thread of FS-LBF-I1.32 is fully engaged in the field-housing entry so the IP67 and mechanical installation boundary is preserved.
The green-yellow lead from FS-LBF-I1.32 follows the shortest practical route to the local equipotential bonding point.
FISCO or Entity parameters for the complete loop containing FS-LBF-I1.32 are checked before the protector is introduced into a Zone 1 fieldbus installation.
User Questions
Is FS-LBF-I1.32 a signal isolator for a fieldbus segment?
No. FS-LBF-I1.32 is a surge-protection device and does not provide circuit separation or protocol conversion. The fieldbus remains one IEC 61158-2 communication path through the protector.
Which housing entry accepts FS-LBF-I1.32?
FS-LBF-I1.32 uses an M20 x 1.5 threaded connection. A 1/2-inch NPT entry belongs to a different housing variant and should not be forced or adapted without an approved installation design.
Why must the earth lead on FS-LBF-I1.32 be kept short?
Surge current from FS-LBF-I1.32 returns through the green-yellow conductor. A long or coiled lead adds inductance and can raise the transient voltage at the protected equipment.
Can FS-LBF-I1.32 be installed in a Zone 1 field housing?
Yes. FS-LBF-I1.32 is documented for intrinsically safe Ex ia use in Zone 1 with FISCO or Entity circuits. The complete loop parameters and enclosure installation still have to meet the applicable certificate conditions.
What must be checked to preserve the IP67 rating of FS-LBF-I1.32?
For FS-LBF-I1.32, verify full M20 thread engagement, the specified sealing arrangement and an undamaged field-housing entry. The rating applies to the completed installation, not to a loose protector.
Should FS-LBF-I1.32 be repaired after a severe surge event?
FS-LBF-I1.32 is not repaired in the field. After a significant transient, inspect the protected loop and earth path and replace the protector if its condition or protective function is uncertain.
Hazardous-Area Product Records
Moore Automation
https://www.mvme.cn/Moore Automation aligns complete model identity, available technical documents and delivery records for Pepperl+Fuchs FS-LBF-I1.32. Exact record control and international communication keep the thread, protection rating and hazardous-area identity together for this specialized field component.
Associated Products
| Control & Process | PLC & I/O | Monitoring & Network | Drives & Power |
|---|---|---|---|
| 01Horner HE800JCM200 | 16GE IC630MDL351 | 31Siemens 6ES7392-1AJ00-0AA0 | 46Allen-Bradley 22A-D2P3N104 |
| 02Foxboro P0926GW | 17Horner HE800WCM802 | 32GE IC630MDL354 | 47Emerson A3311-022-000 |
| 03ICS Triplex T8300 | 18Foxboro RH924YA | 33Horner HE800GCM911 | 48ABB DI820 |
| 04Allen-Bradley 22A-A5P0N104 | 19ICS Triplex T8830 | 34Foxboro FBM201C | 49GE IC630MDL366 |
| 05Emerson A6110 | 20Allen-Bradley 22A-B2P3N104 | 35Allen-Bradley 22A-B8P0N104 | 50Foxboro P0926EQ |
| 06ABB AO815 | 21Emerson A6220 | 36Emerson A6370D | 51Allen-Bradley 22A-D4P0N104 |
| 07Siemens 6ES7336-1HE00-0AB0 | 22ABB AO845A | 37ABB DI811 | 52Emerson EZ1081-04-00-010 |
| 08GE IC630MDL327 | 23Siemens 6ES7390-1AE80-0AA0 | 38Siemens 6ES7392-1AM00-0AA0 | 53ABB DI821 |
| 09Horner HE800JCM205 | 24GE IC630MDL352 | 39GE IC630MDL356 | 54GE IC630MDL367 |
| 10Foxboro FCP280 | 25Horner HE800WCM900 | 40Foxboro FBM201D | 55Foxboro P0914ST |
| 11ICS Triplex T8800 | 26Foxboro FBM201B | 41Allen-Bradley 22A-D1P4N104 | 56Allen-Bradley 22A-D6P0N104 |
| 12Allen-Bradley 22A-A8P0N104 | 27ICS Triplex T8850 | 42Emerson A6371-10 | 57Emerson EZ1081-03-00-010 |
| 13Emerson A6210 | 28Allen-Bradley 22A-B5P0N104 | 43ABB DI814 | 58ABB DI825 |
| 14ABB AO820 | 29Emerson A6312 | 44GE IC630MDL357 | 59GE IC630MDL368 |
| 15Siemens 6ES7336-4GE00-0AB0 | 30ABB DI810 | 45Foxboro FBM202 | 60Foxboro FBM203 |







No related record found