Bently Nevada 3500/92-04-01-01 Communication Gateway
ETHERNET TCP/IP · RS232/422/485 · MODBUS MAP
Product Introduction
Product identityBently Nevada 3500/92-04-01-01 is the 3500 Communication Gateway configuration that exposes rack measurements, module status and alarm status to a host system. The 04 I/O option combines Ethernet with an RS485 Modbus interface, while the 01 memory and approval fields complete the order string.
On the network side, Bently Nevada 3500/92-04-01-01 uses Ethernet TCP/IP and Modbus/TCP through an RJ-45 connection, while the RS485 Modbus path connects to the serial host interface. Rack data is collected over the internal high-speed network and updated at a rate not exceeding one second for all rack modules.
The front OK and TX/RX indicators on Bently Nevada 3500/92-04-01-01 show gateway and rack communication state. The gateway reads data from monitor modules; it does not replace their measurement or alarm evaluation functions.
Technical Information
Verified data| Technical item | Value |
|---|---|
| Brand | Bently Nevada |
| Product type | 3500 Communication Gateway |
| Model | 3500/92-04-01-01 |
| I/O option | 04 Ethernet/RS485 Modbus I/O module |
| Memory option | 01 Low Memory |
| Approval option | 01 CSA/NRTL/C |
| Data source | Rack measured values, module status and alarm status |
| Update time | Not exceeding 1 second for all rack modules |
| Ethernet | 10 Mbps, IEEE 802.3 |
| Ethernet protocol | Ethernet TCP/IP and Modbus/TCP |
| Ethernet connection | RJ-45 10BASE-T |
| Serial protocol | Modbus RTU |
| Serial interface | RS485 |
| Main board dimensions | 241 × 24.4 × 242 mm |
| Main board weight | 0.82 kg |
| I/O module dimensions | 241 × 24.4 × 99.1 mm |
| I/O module weight | 0.44 kg |
| Rack space | One full-height front slot and one full-height rear I/O slot |
| Operating temperature | -30 °C to +65 °C |
| Storage temperature | -40 °C to +85 °C |
| Humidity | 95%, non-condensing |
Communication and Connectivity
Product focusBently Nevada 3500/92-04-01-01 maps internal rack data to Ethernet and RS485 Modbus paths.
The RJ-45 port carries 10BASE-T Ethernet TCP/IP and Modbus/TCP traffic. The RJ-45 path is the Ethernet boundary to the host network.
The 04 I/O module provides the RS485 Modbus interface for the serial host connection. The RS485 path is the serial boundary for Modbus RTU.
The gateway exposes values through the selected protocol while the source monitor modules remain in control of measurement. The gateway maps values without replacing the source module measurement.
Bently Nevada 3500/92-04-01-01 converts the rack data path into Ethernet TCP/IP, Modbus/TCP and RS485 Modbus RTU interfaces. The protocol boundary is defined by the 04 I/O option.
Monitoring and Control
Integration focusBently Nevada 3500/92-04-01-01 presents current values and rack state for host monitoring and control-system data collection.
Collected data includes measured values with timestamps, module statuses and current alarm statuses. The gateway data scope is limited to values and states available from the rack.
The rack collection rate depends on configuration but does not exceed one second for all modules. The update interval describes collection behavior, not a new monitor sampling rate.
The OK and TX/RX LEDs provide local gateway and rack-communication feedback. The LEDs expose gateway and rack communication state locally.
Bently Nevada 3500/92-04-01-01 presents monitor values and statuses to the host without taking over the source module alarm logic. The host data path remains downstream of the monitor modules that create the measurements.
Frequently Asked Questions
Field questionsWhich I/O option is used by Bently Nevada 3500/92-04-01-01?
Within Bently Nevada 3500/92-04-01-01, the 04 option uses the Ethernet/RS485 Modbus I/O module. It is different from the RS232/RS422 and Ethernet/RS232 variants.
Which Ethernet protocol does Bently Nevada 3500/92-04-01-01 use?
On Bently Nevada 3500/92-04-01-01, the Ethernet path supports Ethernet TCP/IP and Modbus/TCP through the RJ-45 10BASE-T connection.
What does the RS485 interface on Bently Nevada 3500/92-04-01-01 carry?
In Bently Nevada 3500/92-04-01-01, the RS485 interface carries the Modbus RTU serial path between the gateway and the connected host system.
What rack data can Bently Nevada 3500/92-04-01-01 expose?
For Bently Nevada 3500/92-04-01-01, the gateway collects current measured values with timestamps, module statuses and current alarm statuses from the 3500 rack.
How quickly does Bently Nevada 3500/92-04-01-01 update rack values?
Within Bently Nevada 3500/92-04-01-01, the data collection rate depends on rack configuration but does not exceed one second for all modules in the rack.
Does Bently Nevada 3500/92-04-01-01 perform vibration measurement?
No. Bently Nevada 3500/92-04-01-01 communicates values and states from the rack; the monitor modules perform signal conditioning and alarm evaluation.
Customer Support
Moore AutomationMoore Automation
https://www.mvme.cn/Moore Automation supports exact industrial automation records across control, monitoring, drive and instrumentation categories. Enquiries for Bently Nevada 3500/92-04-01-01 stay linked to the manufacturer and complete order reference.
Selected Products
Mixed-brand selectionContact & Enquiry
Send the complete model and requested quantity with your enquiry.







No related record found