Welcome to Moore Automation Limited

0
Loadding...
 

sales@mvme.cn    Phone: +86 18030175807

Home>ABB>ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives
ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives

ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives Item NO.: 2931447

Write a Review
US$ 1.00
Quantity
Stock ( 28 )

Copy and share this link on social network or send it to your friends

Copy
Request Price & AvailabilitySend the part number and quantity. Our team will confirm stock, condition, lead time and the best quotation.
  • MOQ: 1 piece
  • International shipping
  • 1-year warranty on eligible items
  • Fast response during business hours
Product Name ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives
Item NO. 2931447
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category ABB
Brand ABB
Creation Time 2026-11-10

ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives
ABBABB Drives · ACS580 low-voltage platform

ABB Drives · ACS580 low-voltage platform

ABB ACS580-01-046A-4 / ACS580-01-062A-4 General Purpose Drives

Two exact ABB drive records for 380–480 V three-phase motor control.

ACS580-01-046A-4R3
ACS580-01-062A-4R4
ACS580general purpose drive
01

Product Summary

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 are ABB wall-mounted general purpose drive in the ACS580 family. They accept a three-phase 380–480 V supply, rectify it to the internal DC link and synthesize a variable-frequency three-phase output for controlling an AC motor.

Power for ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 enters through the line terminals, passes through the rectifier and DC-link stage, and leaves through the motor terminals while protective earth and control wiring remain separate paths. The two order codes remain separate because their current ratings, frame sizes and cable terminations differ.

For installation, ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 use R3 / R4 frame executions. Cable conductor range, terminal torque, cooling clearance and upstream protection are selected from the installed frame; commissioning then confirms motor data, rotation direction, control source and protective functions before the driven machine is released.

02

Technical Details

Technical item ACS580-01-046A-4 ACS580-01-062A-4
Brand ABB
Product name ACS580 wall-mounted general purpose drive
Drive family ACS580
Voltage class 380–480 V AC, three-phase
Input frequency 48–63 Hz
Motor output Three-phase variable voltage and frequency
Control interface Local panel and control terminals
Installation environment Indoor electrical enclosure / wall mounting
Frame size R3 R4
Nominal current 45 A 62 A
Maximum current 67.9 A 81 A
Nominal motor power 22 kW 30 kW
Light-duty current 42.8 A 58 A
Heavy-duty current 37.7 A 45 A
Input cable range 1.5–35 mm² 10–70 mm²
Power-terminal torque 2 N·m 6 N·m
Ambient basis 40 °C rating; derate above stated limit
Country Finland
03

System Integration

System Integration

The operating behavior of ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 is defined by the relationship between the line supply, DC-link conversion, motor output and configured control source.

01

Power conversion path

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 convert fixed-frequency three-phase input into a controlled motor waveform; line protection, motor cable and earthing are sized for the exact current and frame execution.

02

Control and feedback

Start, stop and reference commands can be assigned to the local panel or control terminals, while status and fault information report whether the requested motor command has been accepted.

03

Load-dependent selection

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 separate nominal, light-duty and heavy-duty operation so current demand, motor power and overload behavior are matched to the mechanical load rather than chosen from kW alone.

04

Diagnostics and Protection

Diagnostics and Protection

Commissioning ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 requires the correct frame-specific wiring work and an ordered verification sequence; the numerical ratings are applied to actual conductors, load and protection.

01

Plan while de-energized

Isolate the line supply, wait for the DC link to discharge and verify zero voltage before opening ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4. Record the existing control source, motor data and cable positions.

02

Wire by frame execution

Use the documented conductor range and terminal torque for the installed frame. Keep line, motor, control and protective-earth conductors in their assigned routes, with shield termination and cooling clearances intact.

03

Commission the motor path

Enter the motor nameplate data, check direction uncoupled where possible, prove start/stop and reference selection, then observe current and fault status under a controlled load before normal service.

05

Customer Questions

What should be checked when ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 will not start after replacement?

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 should be checked for charged control power, cleared faults, the selected local or remote command source, active interlocks and a valid speed reference before motor wiring is disturbed.

Why can ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 trip when the motor starts even though the kW rating looks correct?

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 selection must also match motor current, acceleration time and load torque. Confirm entered motor data, mechanical freedom and the applicable nominal or heavy-duty current rating.

How is safe access verified before wiring ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4?

For ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4, isolate all line and external control supplies, wait the prescribed DC-link discharge interval and measure the DC terminals before touching power conductors.

What causes the motor direction to be wrong on ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4?

If ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 runs correctly but rotation is reversed, verify the commanded direction and motor phase sequence. Correct the documented connection only while the drive is isolated and discharged.

Why should terminal torque be checked by frame on ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4?

ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 uses frame-dependent conductor sizes and terminal hardware. Applying a torque from another frame can leave a high-resistance joint or damage the terminal.

What should be recorded before commissioning ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4?

Record the complete ABB ACS580-01-046A-4 / ABB ACS580-01-062A-4 order code, frame, motor nameplate values, control source, cable sizes, protection device and parameter backup so the restored drive can be checked against the installed machine.

06

Obsolete Parts Support

Moore Automation

https://www.mvme.cn

Moore Automation records older or difficult-to-source identifiers with their suffixes and photographs without implying guaranteed availability.

The complete manufacturer, model, requested quantity and destination remain attached to one record for consistent review.

EXACT MODELComplete identifier retained
REQUEST RECORDQuantity and destination linked
SUPPORTING FILESAvailable photographs retained
07

Related Products

Triconex8311
ABB3HAC029032-004
Rockwell Automation1756-A4
HoneywellFC-SDI-1624
Bently Nevada330101-00-08-05-02-00
Schneider Electric140CPU67160
YokogawaAAI835-S50/K4A00
GEIC200CBL500
Allen-Bradley1734-SSI
B&RX20AT4222
Bosch RexrothHCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW
FoxboroFBM217
HIMAF6250
MotorolaMVME162PA-252SE
ProSoftMVI69L-MBTCP
Triconex3721
ABB3HAC029034-004
Rockwell Automation1756-IA16
HoneywellFC-SDOL-0424
Bently Nevada330101-00-08-05-02-05
Schneider Electric140CPU67260
YokogawaAAI841-H50
GEIC200CHS022P
Allen-Bradley1734-TB
B&R4PPC50.101E-13B
Bosch RexrothHCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW
FoxboroFBM218
HIMAF6705
MotorolaMVME167
ProSoftPLX31-EIP-MBS
ABB3HAC029034-006
Rockwell Automation1756-A7
HoneywellFC-TPSU-2430
Bently Nevada330101-00-08-10-02-00
Schneider Electric140CRA93100
YokogawaAAP135-S50
GEIC200CPUE05-GK
Allen-Bradley1734-TBS
B&RX20AT6402
Bosch RexrothHCS01.1E-W0008-A-03-B-ET-EC-NN-L4-NN-FW
FoxboroFBM219
HIMAF6706
MotorolaMVME167-02B
ProSoftPLX31-EIP-MBS4
ABB3HAC029236-001
Rockwell Automation1756-IB16IF
HoneywellFC-TSDI-16UNI
Bently Nevada330101-00-08-10-02-05
Schneider Electric140CRP31200
YokogawaAAV141-S50/K4A00
GEIC200ERM002G
Allen-Bradley1734-VHSC24
B&R4PPC70.0573-20W
Bosch RexrothHCS01.1E-W0013-A-02-B-ET-EC-NN-L3-NN-FW
FoxboroFBM228
HIMAF7126
MotorolaMVME167-032A
ProSoftPLX31-EIP-MBTCP
ABB3HAC030211-001
Rockwell Automation1756-CN2R
08

Enquiry Details

Moore Automation

Send the complete model and requested quantity.

ManagerLeonia

No related record found

You May Also Like

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.