Product Description
Yokogawa CP471-00 is a processor module for CENTUM field control units. It provides the control-processing layer for supported field control stations and works with the Control Function for Field Control Station software environment.
Inside a duplexed field control unit, CP471-00 can operate as one member of a two-module redundant processor pair. The arrangement preserves separate processor paths while the field control unit maintains its dual-redundant Vnet/IP interface to the plant control network.
For software and bus-coupler alignment, CP471-00 belongs with R5.01-or-later control-function software and an EC401 ESB bus coupler of style code S3 or later. The -00 suffix identifies the non-explosion-protected, basic version, so the complete model string remains part of the hardware record.
Technical Specifications
| Technical Item | CP471-00 |
|---|---|
| Brand | Yokogawa |
| Product Type | CENTUM field control processor module |
| Brand Country | Japan |
| Suffix Configuration | No explosion protection; basic type |
| Control Function Version | R5.01 or later; version-specific patches apply |
| Supported Field Control Units | AFV30S/D, AFV40S/D; R6 also supports A2FV50S/D, A2FV70S/D and A2BE1D |
| ESB Bus Coupler Boundary | EC401 style code S3 or later |
| Processor Redundancy | Two-module dual-redundant configuration supported |
| Network Interface | Dual-redundant Vnet/IP through the field control unit |
| Main-Memory Backup | Maximum 72 hours |
| Recharge Time | Minimum 48 hours |
| External Envelope | 32.8 × 149 × 199.5 mm |
| Approximate Weight | 0.7 kg |
| Standard Accessory | T9044AR processor-module modification history label, quantity 1 |
CENTUM Field Control Placement
Processor placement follows the field-control-unit generation.
CP471-00 is seated in the processor position of the supported CENTUM field control unit rather than treated as a standalone controller. R5 stations cover AFV30 and AFV40 families, while R6 expands the documented placement to A2FV50, A2FV70 and the A2BE1D base plate.
Chassis identity first
Before installing CP471-00, match the station and base-plate designation to the documented R5 or R6 hardware family. This keeps the processor position aligned with the intended CENTUM generation.
ESB path style boundary
The ESB path used with CP471-00 requires an EC401 coupler at style code S3 or later. The style check belongs to the hardware record because an earlier EC401 is outside the documented processor arrangement.
Dual-Redundant Processor Continuity
Two CP471-00 modules form the documented dual-redundant processor set in a duplexed field control unit. The pair works as one control-processing arrangement without mixing processor generations.
When the redundant CP471-00 arrangement is healthy, one CP471 module can be replaced online by the user. The running partner preserves the processor path while the replacement is handled within the documented redundant configuration.
A CP471-00 must not coexist with a CP461 in one redundant pair, and an installed CP471 must not be replaced by a CP461. Converting a CP461 pair to CP471 hardware requires the specified software, patches and authorized-service procedure.
Frequently Asked Questions
What does the -00 suffix identify on CP471-00?
For CP471-00, the first 0 identifies the non-explosion-protected version and the second 0 identifies the basic type. Keeping both suffix positions prevents the hardware record from being confused with an explosion-protected or G3-option variant.
Which CENTUM field control units accept CP471-00?
CP471-00 is documented for AFV30S/D and AFV40S/D field control units, with R6 support also covering A2FV50S/D, A2FV70S/D and A2BE1D. The installed station generation should be confirmed before assigning the processor.
Why does EC401 style matter when CP471-00 is installed?
The ESB bus path used with CP471-00 requires EC401 style code S3 or later. An earlier coupler style is outside the documented combination, even if the physical connector arrangement appears similar.
Can CP471-00 run with every R5 software revision without a patch?
CP471-00 requires Control Function for Field Control Station R5.01 or later, and the early R5/R6 revisions listed in the product specification require their corresponding patches. Software revision and patch status should therefore be checked together.
May CP471-00 share a redundant pair with CP461?
No. CP471-00 and CP461 cannot coexist in the same dual-redundant processor configuration. A paired CP461 conversion is handled as a controlled hardware-and-software transition, not a one-module substitution.
How long is CP471-00 main memory protected after power loss?
The documented main-memory backup period for CP471-00 is a maximum of 72 hours. Restoring the full backup condition requires at least 48 hours of recharge time, so the elapsed powered period matters after extended storage or outage.
Our Services
Moore Automation
https://www.mvme.cn/Moore Automation supports industrial teams with clear product records, document coordination and responsive communication. For Yokogawa CP471-00, the exact model, processor family and requested destination remain together from the first contact through shipment coordination.
Full model retained
Available records aligned
Delivery details coordinated
Recommended Products
| Control Systems | PLC & I/O | Monitoring | Drive & Network |
|---|---|---|---|
| 01Siemens 6ES7288-1SR20-0AA1 | 16Motorola MVME162-212 | 31ProSoft ILX56-PBM | 46Yokogawa SAI143-H63/PRP |
| 02ABB PM5012-R-ETH | 17Foxboro FBM203B | 32Vibro-Meter RPS6U | 47Woodward 8440-2082 |
| 03Allen-Bradley 1769-L24ER-QB1B | 18Siemens 6ES7288-1SR30-0AA1 | 33Motorola MVME162-520 | 48ProSoft PLX31-EIP-MBS |
| 04Bently Nevada 330130-040-00-05 | 19ABB PM5032-T-ETH | 34Foxboro FBM203C | 49Vibro-Meter MPC4 |
| 05Emerson 5X00270G01 | 20Allen-Bradley 1769-L24ER-QBFC1B | 35Siemens 6ES7288-1SR40-0AA1 | 50Motorola MVME147-011 |
| 06GE IC695CPE330 | 21Bently Nevada 330130-046-00-06 | 36ABB PM5052-R-ETH | 51Foxboro FBM203D |
| 07Honeywell FC-SAI-1620M | 22Emerson VE4002S1T2B1 | 37Allen-Bradley 1769-L27ERM-QBFC1B | 52Siemens 6ES7288-1SR60-0AA1 |
| 08Triconex 3009X | 23GE IC695CPE400 | 38Bently Nevada 330130-080-13-05 | 53ABB PM5052-T-ETH |
| 09HIMA F35 | 24Honeywell CC-PUIO31 | 39Emerson 5X00419G02 | 54Allen-Bradley 1769-L30ER |
| 10B&R X20CP1586 | 25Triconex 4610X | 40GE IC695CPE310 | 55Bently Nevada 330130-085-03-05 |
| 11Bosch Rexroth DDS02.1-W100-D | 26HIMA F8650X | 41Honeywell CC-PAIL51 | 56Emerson SE4304T01 |
| 12Yokogawa AAI143-H50/K4A00 | 27B&R X20CP1585 | 42Triconex 8120X | 57GE IC695CPE305 |
| 13Woodward 2301A | 28Bosch Rexroth HCS01.1E-W0009-A-02-B-ET-EC-NN-L3-NN-FW | 43HIMA F7131 | 58Honeywell FC-UGAO01 |
| 14ProSoft MVI56E-MCM | 29Yokogawa ADV151-E60/D5A00 | 44B&R X20CP1584 | 59Triconex 4701X |
| 15Vibro-Meter TQ902 | 30Woodward 8200-188 | 45Bosch Rexroth HCS02.1E-W0054-A-03-NNNN | 60HIMA F3330 |






No related record found