Command conversion
Each module converts sixteen controller data words into bipolar voltage outputs, updating the complete set every 10 ms.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Yokogawa AAV542-S50 S2 / AAV544-S50 S2 | 16-Channel Voltage Output Modules |
| Item NO. | 2929197 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | YOKOGAWA |
| Brand | YOKOGAWA |
| Creation Time | 2026-11-02 |
YOKOGAWA · CENTUM ENGINEERING RECORD
Yokogawa AAV542-S50 S2 and Yokogawa AAV544-S50 S2 are sixteen-channel -10 to +10 V analog output modules for CENTUM field control stations. AAV542-S50 S2 uses a non-isolated output structure, whereas AAV544-S50 S2 isolates the channels from the system so the two models address different field-circuit arrangements.
Controller output words reach Yokogawa AAV542-S50 S2 as a common module image and are converted into sixteen voltage signals for loads of 10 kΩ or greater. Yokogawa AAV544-S50 S2 performs the same command conversion with 5 kΩ minimum loads and a 1500 V AC channel-to-system withstand boundary.
Both Yokogawa AAV542-S50 S2 and Yokogawa AAV544-S50 S2 update outputs every 10 ms and settle in 40 ms, but their isolation, load and current-consumption requirements are not interchangeable. The wiring plan therefore follows the exact model rather than the shared voltage range.
| TECHNICAL ITEM | AAV542-S50 S2 | AAV544-S50 S2 |
|---|---|---|
| Brand | Yokogawa | |
| Model | AAV542-S50 S2 | AAV544-S50 S2 |
| Nameplate Suffix | S2 (commonly seen) | S2 (commonly seen) |
| Product Name | 16-channel non-isolated voltage output module | 16-channel isolated voltage output module |
| Country | Japan | |
| Output Channels | 16 | |
| Output Signal | -10 to +10 V DC | |
| Isolation | Non-isolated | Isolated channels |
| Withstand Voltage | Not applicable | 1500 V AC for 1 minute |
| Minimum Load | 10 kΩ | 5 kΩ |
| Accuracy | Larger of ±0.3% FS and ±12 mV | |
| Update Period | 10 ms | |
| Output Step Response | 40 ms | |
| Temperature Drift | Larger of ±0.1%/10 °C and ±10 mV/10 °C | |
| Current Consumption | 450 mA at 5 V | 860 mA at 5 V |
| External Connection | Pressure clamp terminal, KS cable or MIL connector cable | |
| Dimensions | 32.8 × 130 × 107.5 mm | |
| Weight | Approx. 0.20 kg | |
AAV542-S50 S2 and AAV544-S50 S2 share the same voltage span and timing but differ at the field-circuit boundary.
Each module converts sixteen controller data words into bipolar voltage outputs, updating the complete set every 10 ms.
AAV542-S50 S2 requires at least 10 kΩ per output; AAV544-S50 S2 supports 5 kΩ or greater, so receiver impedance affects model selection.
AAV544-S50 S2 provides channel-to-system withstand separation. AAV542-S50 S2 does not, so grounding and common potentials belong to the external design.
Install the selected module by matching its isolation class and receiver load before conductors are landed.
List every receiving device, its input impedance and grounding reference; confirm that each circuit satisfies the chosen module load limit.
De-energize the node, seat AAV542-S50 S2 or AAV544-S50 S2 in the assigned slot, then connect the documented terminal or cable assembly without mixing channel returns.
Apply module power first, command a safe value on one channel, confirm polarity and measured voltage, and then release the remaining outputs in controlled groups.
Yokogawa AAV542-S50 S2 / AAV544-S50 S2 use minimum loads of 10 kΩ and 5 kΩ respectively; the connected receiver impedance must satisfy the exact selected module.
No. Yokogawa AAV542-S50 S2 / AAV544-S50 S2 share the voltage range, but AAV542-S50 S2 is non-isolated and AAV544-S50 S2 has isolated channels.
For Yokogawa AAV542-S50 S2 / AAV544-S50 S2, check the receiver load, wiring capacitance, output update path and the documented 40 ms step response before treating the module as faulty.
Yokogawa AAV542-S50 S2 / AAV544-S50 S2 should be installed and terminated under the approved de-energized procedure so an output conductor cannot be shorted or assigned to the wrong return.
For Yokogawa AAV542-S50 S2 / AAV544-S50 S2, verify output polarity, zero and full-scale commands, actual receiver impedance and the result at the connected input before releasing all channels.
No. Yokogawa AAV542-S50 S2 / AAV544-S50 S2 share the external envelope, but isolation, load and current consumption differ and must be checked in the project design.
Moore Automation organizes industrial-part enquiries around complete model strings, requested quantities and destination details. Supporting photographs and available technical files can remain connected to the same record for review.