Pulse acquisition
AAP149-S00 S1 collects sixteen pulse channels at up to 6 kHz. AAP849-S00 S1 collects eight channels at up to 12 kHz and updates their controller image faster.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Yokogawa AAP149-S00 S1 / AAP849-S00 S1 | Pulse Input and Pulse/Analog I/O Modules |
| Item NO. | 2929198 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | YOKOGAWA |
| Brand | YOKOGAWA |
| Creation Time | 2026-11-02 |
YOKOGAWA · CENTUM ENGINEERING RECORD
Yokogawa AAP149-S00 S1 and Yokogawa AAP849-S00 S1 are pulse-processing modules for CENTUM field control stations. AAP149-S00 S1 acquires sixteen open-collector pulse inputs for PM1-compatible processing, while AAP849-S00 S1 couples eight pulse inputs with eight 4 to 20 mA outputs for PAC-compatible loops.
Pulse transitions enter Yokogawa AAP149-S00 S1 at up to 6 kHz and are detected on the trailing edge before the module updates controller data every 2 ms. Yokogawa AAP849-S00 S1 accepts pulse trains up to 12 kHz, updates the input image every 1 ms and separately converts eight controller commands into analog current outputs.
The dedicated cable is part of the signal path for Yokogawa AAP149-S00 S1 and Yokogawa AAP849-S00 S1. AAP849-S00 S1 also requires output-loop load and open-circuit behavior to be checked, whereas AAP149-S00 S1 has no analog output circuits.
| TECHNICAL ITEM | AAP149-S00 S1 | AAP849-S00 S1 |
|---|---|---|
| Brand | Yokogawa | |
| Model | AAP149-S00 S1 | AAP849-S00 S1 |
| Nameplate Suffix | S1 | S1 |
| Product Name | 16-channel pulse input module | 8-pulse-input / 8-analog-output module |
| Country | Japan | |
| Input Channels | 16 | 8 |
| Output Channels | None | 8 |
| Pulse Input | Open-collector transistor contact | |
| Input Frequency | 0 to 6 kHz | 0 to 12 kHz |
| Detection Edge | Trailing edge | |
| Input Update | 2 ms | 1 ms |
| Analog Output | Not applicable | 4 to 20 mA |
| Output Load | Not applicable | 0 to 750 Ω |
| Output Accuracy | Not applicable | ±48 µA |
| Output Update | Not applicable | 10 ms |
| Output Step Response | Not applicable | 40 ms |
| Current Consumption | 400 mA at 5 V | 310 mA at 5 V plus 250 mA at 24 V |
| External Connection | Dedicated KS2 cable | Dedicated KS1 cable |
| Dimensions | 32.8 × 130 × 127.2 mm | |
| Weight | Approx. 0.30 kg | |
The modules organize pulse events differently because only AAP849-S00 S1 adds an analog control path.
AAP149-S00 S1 collects sixteen pulse channels at up to 6 kHz. AAP849-S00 S1 collects eight channels at up to 12 kHz and updates their controller image faster.
Trailing-edge detections become controller pulse data through the dedicated cable and configured channel mapping; the controller, not the module face, supplies the engineering interpretation.
AAP849-S00 S1 converts eight controller values into 4 to 20 mA outputs. AAP149-S00 S1 stops at pulse acquisition and cannot drive analog loops.
AAP149-S00 S1 and AAP849-S00 S1 sit between open-collector pulse sources and their CENTUM control functions, with different cable and output requirements.
The sensor or pulse source must present the documented open-collector signal and maintain the expected trailing-edge behavior across the configured frequency range.
KS2 belongs to AAP149-S00 S1; KS1 belongs to AAP849-S00 S1. Cable identity and connector orientation must be verified before the module is seated.
For AAP849-S00 S1, each 4 to 20 mA receiver remains within 750 Ω and circuit-open detection is included in commissioning checks.
No. Yokogawa AAP149-S00 S1 / AAP849-S00 S1 differ in channel count, cable type and whether analog outputs are required, so the complete input/output arrangement must be matched.
For Yokogawa AAP149-S00 S1 / AAP849-S00 S1, verify open-collector wiring, trailing-edge quality, frequency limit, common reference, cable assignment and the controller sampling configuration.
Yokogawa AAP149-S00 S1 / AAP849-S00 S1 use KS2 and KS1 dedicated cables respectively; the two cable assignments should not be exchanged.
No. Yokogawa AAP149-S00 S1 / AAP849-S00 S1 provide no analog output and eight 4 to 20 mA outputs respectively.
For Yokogawa AAP149-S00 S1 / AAP849-S00 S1, inject a known low-rate pulse first, confirm ordered counts, then raise frequency within the specified limit; also verify each AAP849-S00 S1 current output under its actual load.
Only the AAP849-S00 S1 part of Yokogawa AAP149-S00 S1 / AAP849-S00 S1 has current outputs; check loop continuity, polarity and load when its output current falls below the open-detection threshold.
Moore Automation works with multi-brand automation references and keeps each enquiry tied to the requested manufacturer and full model. This structure helps distinguish similar modules, option codes and generations during commercial review.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.