Product Name GE IC200MDL650M VersaMax 32-Point 24 V DC Positive/Negative Logic Input Module
Item NO. 2944335
Weight 0.1 kg = 0.2205 lb = 3.5274 oz
Category GE
Brand GE
Creation Time 2026-11-23

GE IC200MDL650M VersaMax 32-Point 24 V DC Positive/Negative Logic Input Module
GEVersaMax Modular I/O
4×8input bank structure
Grouped input module

GE IC200MDL650M VersaMax 32-Point 24 V DC Positive/Negative Logic Input Module

Thirty-two field inputs with four common references and software-selectable filtering.

Product Information

GE IC200MDL650M is a VersaMax 32-point 24 V DC discrete input module arranged as four banks of eight points. Each bank has a dedicated common, allowing the terminal map to preserve four separate field-circuit references.

With GE IC200MDL650M, a bank may be wired for positive-logic or negative-logic operation. The module converts the 32 terminal states into one controller input image while the carrier provides the physical field connection.

GE IC200MDL650M derives operating power from the backplane and does not require a separate external module supply. Point LEDs show the individual states, and the configured filter interval determines how long a field transition must persist before acceptance.

Technical Data

GE IC200MDL650M
Specification Value
Brand GE
Product Name VersaMax 32-Point 24 V DC Positive/Negative Logic Input Module
Series VersaMax Modular I/O
Input Count 32
Grouping Four groups of eight
Logic Modes Positive and negative
Nominal Voltage 24 V DC
Voltage Range 0 to 30 V DC
On-State Voltage 15 to 30 V DC
Off-State Voltage 0 to 5 V DC
On-State Current 2.0 to 5.5 mA
Specification Value
Off-State Current 0 to 0.5 mA
Input Impedance 10 kΩ maximum
Response Time 0.5 ms maximum before configured filter
Filter Choices 0, 1.0 or 7.0 ms
Module Supply Backplane powered
5 V Backplane Load 50 mA maximum
Optical Isolation 250 V AC continuous; 1500 V AC for 1 minute
Group Isolation 250 V AC continuous; 1500 V AC for 1 minute
Point Isolation None
Indicators 32 point LEDs and OK LED

Four-Bank Input Mapping

GE IC200MDL650M preserves four electrical common groups while presenting a continuous 32-point controller image.

1-8

First common group

The first eight inputs share one field reference and occupy the first segment of the input map.

9-24

Middle two groups

Two independent groups cover the center 16 points, preventing their commons from being assumed as one conductor.

25-32

Fourth common group

The final eight points complete the module image with their own field reference.

Diagnostic Indicators

The front indications on GE IC200MDL650M separate per-point field-state visibility from the module backplane-power condition.

POINT

One LED for every input

A lit point indicator reports the state detected at that input channel after the field circuit is interpreted.

OK

Backplane presence

The OK indicator confirms module operating power from the carrier but does not certify field voltage at a point.

FILTER

Controller acceptance

A transition reaches the input image only after it satisfies the selected filter interval.

Product Questions

Why do several GE IC200MDL650M inputs fail together?

When several GE IC200MDL650M points in one bank fail, check that bank common, field reference and terminal connection before treating the channels as separate faults.

Can GE IC200MDL650M mix sourcing and sinking devices?

GE IC200MDL650M supports positive- or negative-logic wiring by group; document each common and do not mix current directions inside a group without a verified circuit design.

What causes delayed input recognition on GE IC200MDL650M?

The GE IC200MDL650M configured filter adds qualification time; compare the selected 0, 1 or 7 ms interval with the source pulse width.

Why can the GE IC200MDL650M OK LED be on with no field activity?

The GE IC200MDL650M OK LED reflects backplane power, whereas field activity depends on sensor voltage, common wiring and individual terminals.

How should a three-row carrier be documented for GE IC200MDL650M?

Use the GE IC200MDL650M three-row terminal diagram and record the A/B terminal positions for all four input groups and commons.

Which suffix should appear on a GE IC200MDL650M order record?

Keep GE IC200MDL650M complete on the order, label and receiving record, together with quantity, carrier type and destination.

Revision Record Coordination

Moore Automation

https://www.mvme.cn/

Moore Automation keeps quotation, packing and tracking information tied to the exact revision supplied by the customer. Reliable carriers and shipment updates support domestic and international delivery while GE IC200MDL650M remains distinct from nearby VersaMax revisions.

Suffix controlThe complete revision stays visible
Shipment trackingCarrier progress can be followed
Global deliveryInternational destinations supported

No related record found

You May Also Like

Copyright © 2004–2026 www.mvme.cn. All rights reserved.

Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.