Cooling is by convection, so avoid placing heat-producing equipment directly below the rack or blocking the airflow path. Keep the cabinet within the documented temperature and non-condensing humidity envelope.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | GE Fanuc IC610CHS101 Series One 5-Slot AC-Powered Rack |
| Item NO. | 2908093 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | GE |
| Brand | GE |
| Creation Time | 2026-09-14 |
IC610CHS101 is a five-slot powered rack for GE Fanuc Series One and Series One Plus controller hardware. It combines the module enclosure, backplane and AC power source in one compact assembly for installations that do not require a separate expansion rack.
The catalog designation is important during replacement: this version has no expansion connection, no 24 VDC user terminals and no Run relay. Those limits distinguish it from other Series One rack configurations that may look similar in a cabinet.
| Technical Item | Specification Value |
|---|---|
| Brand | GE Fanuc |
| Model | IC610CHS101 |
| Product Type | Series One 5-slot powered rack |
| Brand Country | United States |
| AC Input | 115/230 VAC ±15% |
| Input Frequency | 47–63 Hz |
| Maximum Load | 30 VA |
| Internal Output | 0.4 A at 5 VDC; 0.6 A at 9 VDC; 0.2 A at 24 VDC |
| Operating Temperature | 0–60°C |
| Storage Temperature | −10–70°C |
| Relative Humidity | 5–95%, non-condensing |
| Completed Rack Size | 290 × 120 × 140 mm (11.4 × 4.7 × 5.5 in) |
| Completed Rack Weight | <2.0 kg (<4.5 lb) |
Mount the rack horizontally so natural convection can move air through the enclosure. The manual calls for 75 mm above, 100 mm below and about 75 mm at the sides; allow 150 mm between vertically stacked racks.
Use the figure beside this text to preserve the manufacturer’s heat-dissipation clearances. The rack is a local powered enclosure and is not approved as an expansion rack.
Cooling is by convection, so avoid placing heat-producing equipment directly below the rack or blocking the airflow path. Keep the cabinet within the documented temperature and non-condensing humidity envelope.
Before energizing a replacement, confirm the input-voltage selector and protective-earth connection. Provide sufficient cabinet space for field wiring without reducing the specified ventilation gaps.
No. The manual identifies IC610CHS101 as a five-slot powered rack without expansion capability.
Confirm the rack input-voltage selection, protective earth, module seating and unobstructed ventilation clearances.
No. The catalog description specifically states that this rack has no 24 VDC terminals.
The assembly uses natural convection. Free space above, below and beside the rack helps prevent heat from accumulating around installed modules.
Record the complete rack catalog number and the selected AC input setting; do not identify it only by its five-slot appearance.
Moore Automation supplies catalog-specific industrial automation products, including hard-to-find and discontinued parts. Customers can request 100% original products with fast delivery, a 1-year warranty and a 12-hour online response.
Send the complete catalog number and required quantity for product identification and order assistance.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found