GE Fanuc IC5005TAW1000 / IC5005TAW4000 15-inch CIMPLICITY Stations
Product Description
The IC5005 platform integrates a 15-inch operator display and industrial computer for running machine visualization, alarm, data-entry and communication functions within the CIMPLICITY Station family.
IC5005TAW1000 includes Machine Edition development and runtime software with the documented 8000-I/O capacity. This configuration supports both engineering work and execution of the completed operator application.
IC5005TAW4000 is the runtime-only configuration with a 1500-I/O capacity. The display class remains the same, but its software role is limited to operating an already-developed project.
Technical Specifications
Shared specifications
- Product family
- CIMPLICITY Station
- Display class
- 15-inch panel computer
- Hardware series
- IC5005 standard station
- Operating platform
- Windows 2000
- Mounting
- Vertical panel installation
Model-specific differences
- Software role
- Machine Edition development and runtime
- Documented capacity
- 8000 I/O
- Local engineering
- Included
- Software role
- Machine Edition runtime
- Documented capacity
- 1500 I/O
- Local engineering
- Not included
Replacement Readiness Record
-
Project package
Save the editable project when moving from a development station; a runtime upload may not replace the source archive.
-
Peripheral map
Label serial, Ethernet and removable-media connections before removal.
-
License evidence
Record the installed Machine Edition authorization and original order code.
Same Panel Class, Different Entitlement
Shared configuration
Model-specific configuration
15-inch development and runtime station, 8000-I/O entitlement.
15-inch runtime station, 1500-I/O entitlement.
FAQ
What is lost if an IC5005TAW1000 is replaced by IC5005TAW4000 without review?
The 4000 order is runtime-only and carries the lower 1500-I/O entitlement; the 1000 order includes development and runtime for up to 8000 I/O.
Why is a runtime backup not the same as the IC5005 source project for IC5005TAW1000 / IC5005TAW4000?
A runtime package may operate the machine but omit editable development information. Keep the original Machine Edition source and its revision history.
Which peripheral details matter during a 15-inch station exchange for IC5005TAW1000 / IC5005TAW4000?
Label each Ethernet and serial connection, removable-media device and any special adapter, then record protocol and addressing data.
How should an IC5005 license handover be prepared for IC5005TAW1000 / IC5005TAW4000?
Record the exact order code, installed authorization, license medium or host binding and the approved recovery process before the shutdown.
What should be tested after restoring the IC5005 station for IC5005TAW1000 / IC5005TAW4000?
Open the project, verify controller communications, exercise alarms and recipes, and confirm the intended runtime starts automatically.
When is IC5005TAW4000 the appropriate choice for IC5005TAW1000 / IC5005TAW4000?
Use it for a dedicated 15-inch runtime node whose project remains inside the documented 1500-I/O limit and does not need local development tools.