Sensor entry
RTD, thermocouple, voltage and current inputs enter through channel-specific terminal assignments.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Emerson A6500-TP Temperature and Process Input Card |
| Item NO. | 2944905 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | EMERSON |
| Brand | EMERSON |
| Creation Time | 2026-11-25 |
Emerson A6500-TP is a temperature and process input card for the AMS 6500 ATG machinery protection system. Four galvanically isolated measuring channels accept RTD, thermocouple or process-signal inputs, and the card can supervise as many as eight temperature points when dual-element configurations are used.
Each channel on A6500-TP uses a 24-bit analog-to-digital converter and supports Pt100, Ni100, Ni120 and Cu10 resistance sensors, thermocouple types E, J, K, T and N, 0 to 10 V signals, and 0/4 to 20 mA inputs. The input choice is configured per channel so different process measurements can coexist on one card.
A6500-TP adds two digital inputs, six digital outputs and four current outputs to the measurement path. Internal RS485 communication links the card to A6500-CC system communication hardware, while rack installation in an A6500-SR provides the mechanical and power interface required by the protection system.
| Specification | A6500-TP |
|---|---|
| Brand | Emerson |
| Product Type | Temperature and process input card |
| Brand Country | United States |
| System family | AMS 6500 ATG |
| Measuring channels | 4 galvanically isolated |
| Maximum temperature points | 8 |
| ADC resolution | 24 bit |
| RTD inputs | Pt100, Ni100, Ni120, Cu10 |
| Thermocouple inputs | E, J, K, T, N |
| Voltage input | 0 to 10 V |
| Current input | 0/4 to 20 mA |
| Digital inputs | 2 |
| Digital outputs | 6 |
| Current outputs | 4 |
| Internal communication | RS485 to A6500-CC |
| Rack format | 3U, one slot in A6500-SR |
| Power consumption | Maximum 5 W |
| Protection class | IP20 |
| Operating temperature | -20 to 70 °C with forced cooling; -20 to 55 °C without |
Emerson A6500-TP converts temperature and process signals through four isolated paths so one field circuit does not become the reference for another.
RTD, thermocouple, voltage and current inputs enter through channel-specific terminal assignments.
A 24-bit converter digitizes each selected signal before scaling and alarm evaluation.
Galvanic separation preserves the electrical boundary among field circuits and the monitoring backplane.
Emerson A6500-TP distributes measured values to local outputs and to the AMS 6500 communication layer rather than limiting them to one display path.
Digital inputs receive external states while six digital outputs present configured alarm or status functions.
Four current outputs can reproduce selected process values for another control or recording system.
Internal RS485 transfers channel values and status through A6500-CC to the wider monitoring system.
Check the configured RTD connection and field continuity on Emerson A6500-TP. An open lead can drive the indicated value high, so verify all sensor conductors at the terminal before changing scaling.
On Emerson A6500-TP, reversed thermocouple polarity, mixed extension-wire alloys or an incorrect thermocouple type can create an offset. Confirm the configured E, J, K, T or N type and the complete conductor path.
Yes. Emerson A6500-TP configures its four isolated channels individually, so supported RTD, thermocouple, voltage and current inputs can share the card while retaining their own channel settings.
Confirm the rack procedure, channel trip strategy and output state before removing Emerson A6500-TP. Hot-swap capability protects availability, but the system response to missing measurements still depends on the configured logic.
Emerson A6500-TP may use latching, delay or voting logic around an alarm. Review the channel status, reset conditions and digital-output assignment instead of assuming the contact follows the raw value directly.
Read local channel status on Emerson A6500-TP first. Valid local measurements with missing system data point toward the rack link or A6500-CC path; invalid channel data points toward the sensor input or configuration.
Moore Automation supplies industrial automation and electronic components to customers worldwide. Its product range covers programmable controllers, distributed control systems, human-machine interfaces, servo and drive products, sensors and other essential automation parts from established manufacturers.