Power conversion path
The -02 HCS01 variants accept the documented 110…230 V mains class and generate a three-phase motor output up to the applied input level. The W0003 and W0006 designations separate the maximum-current capability.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Bosch Rexroth · HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW / HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW · IndraDrive Cs HCS01 Compact Single-Axis Converters |
| Item NO. | 2940319 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | BOSCH |
| Brand | BOSCH |
| Creation Time | 2026-11-17 |
Dual-model configuration brief
Bosch Rexroth HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and Bosch Rexroth HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW are HCS01 compact single-axis drive controllers in the Rexroth IndraDrive Cs system. Each device combines a power section with a Basic control section in one cabinet-mounted unit. Its system responsibility is to convert the incoming AC supply into a controlled three-phase motor output while the control section coordinates motion commands, motor feedback and device status.
On HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW, the ET interface carries Multi-Ethernet communication through X22 and X23, while the EC interface receives motor-encoder feedback through X4. The Basic control section processes these two data paths together with the firmware-assigned digital inputs and outputs at X31. The Bb relay contact at X47.1 and X47.2 then presents the controller's ready-for-operation state to the external control circuit.
Power in HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW enters X3 as single- or three-phase AC 110...230 V and leaves X5 as a controlled three-phase AC 0...230 V motor supply with a 1.1 A UL rated output current. HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW uses the same input-to-output path with a 2.0 A UL rated output current. In both devices, a separate 24 V control supply enters X13 and feeds the control section and the L3 safety option independently of the motor-power path.
| Attribute | HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW | Shared configuration | HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW |
|---|---|---|---|
| Brand | Bosch Rexroth | Shared identity | Bosch Rexroth |
| Product Name | IndraDrive Cs HCS01 compact single-axis converter | Shared product family | IndraDrive Cs HCS01 compact single-axis converter |
| Country | Germany | Brand origin | Germany |
| Maximum current class | 3 A | Variant-specific | 6 A |
| UL rated input current | 1.8 A or 0.6 A | Depends on the permitted mains connection | 2.8 A or 1.2 A |
| UL rated output current | 1.1 A | Variant-specific | 2.0 A |
| Power dissipation at continuous current | 8 W | At minimum switching frequency | 10 W |
| UL rated input voltage | — | 1 or 3 × AC 110…230 V | — |
| Output voltage | — | 3 × AC 0…230 V | — |
| Dimensions and mass | — | 215 × 50 × 196 mm (H × W × D); 0.72 kg | — |
| Control and interfaces | — | B = Basic; ET = Multi-Ethernet; EC = multi-encoder interface; next interface not equipped | — |
| Safety and firmware | — | L3 = Safe Torque Off; other design none; standard control panel; firmware ordered separately | — |
| Operating environment | — | 0…40 °C nominal operation; operation to 55 °C with reduced data; pollution degree 2 | — |
| Standard installation | — | G1 mounting; 90 mm top, 90 mm bottom and 10 mm horizontal clearance | — |
The shared order-code architecture defines how both converters sit between the permitted mains supply, the motor power path, feedback devices, industrial Ethernet communication and the machine safety circuit.
The -02 HCS01 variants accept the documented 110…230 V mains class and generate a three-phase motor output up to the applied input level. The W0003 and W0006 designations separate the maximum-current capability.
ET identifies Multi-Ethernet communication and EC identifies the multi-encoder interface. The exact network protocol, encoder type, cable set and commissioning parameters must match the machine design.
L3 provides Safe Torque Off. The FW suffix identifies the standard control panel arrangement with firmware ordered separately, so replacement planning must include the correct firmware and parameter set.
Mechanical spacing, thermal airflow and switching-frequency-related cable limits should be resolved before a replacement is wired or commissioned.
Both variants share the 215 mm high, 50 mm wide and 196 mm deep housing. Plan the mounting rail and cabinet layout around the standard G1 orientation rather than rotating the converter to fit a constrained space.
Keep at least 90 mm clear above, 90 mm below and 10 mm horizontally. The nominal operating range is 0…40 °C; operation up to 55 °C requires reduced performance data.
For these W0003 and W0006 variants, the documented maximum motor-cable lengths are 40 m at 4 kHz, 20 m at 8 kHz, 15 m at 12 kHz and 5 m at 16 kHz.
Six comparison questions cover the shared configuration and the key differences between the two exact order codes.
HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW is the 3 A maximum-current configuration, while HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW is the 6 A maximum-current configuration. They share the same compact HCS01 architecture, Basic control section, Multi-Ethernet communication, multi-encoder interface and L3 Safe Torque Off option, but their electrical current ratings differ.
HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW should not be treated as automatic substitutes. Confirm the complete order code, material number, motor duty, mains arrangement, overload requirement, feedback, network protocol, safety circuit, firmware and parameter set before approving either configuration.
Both HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW belong to the -02 class for the documented 1- or 3-phase AC 110…230 V input arrangement. The W0003 configuration lists 1.1 A UL rated output current, while the W0006 configuration lists 2.0 A; the full application curves and motor duty remain necessary for selection.
Yes. HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW both use B Basic control, ET Multi-Ethernet communication, the EC multi-encoder interface and L3 Safe Torque Off. The active Ethernet protocol, encoder type, cable set, safety wiring and parameterization still need to match the machine.
HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW share the 215 × 50 × 196 mm housing and standard G1 mounting arrangement. Preserve 90 mm above, 90 mm below and 10 mm horizontally, and check the documented motor-cable limit for the selected switching frequency.
Both HCS01.1E-W0003-A-02-B-ET-EC-NN-L3-NN-FW and HCS01.1E-W0006-A-02-B-ET-EC-NN-L3-NN-FW end in FW, indicating that firmware is ordered separately. Before replacement, verify the firmware release, licensed functions, parameter backup, motor data, network settings, encoder configuration, Safe Torque Off validation and the approved commissioning method.
Moore Automation Limited is an international supplier specializing in PLC, DCS and industrial automation components from established manufacturers. Its single-source supply channel combines an extensive inventory of OEM and certified replacement parts with customer-focused support for global industrial enquiries.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found