B&R X67 system · current input and output channels
B&R X67AM1323 X67 Analog Mixed I/O Module
Product Introduction
B&R X67AM1323 is an IP67 analog mixed I/O module for the X67 system with two 0–20 mA differential inputs and two 0–20 mA outputs. It places current-loop acquisition and current-command generation in one field-mounted station and exchanges their process values, status information and parameters through X2X Link.
On channels 1 and 2, X67AM1323 routes the field current through the differential input stage and 12-bit A/D converter before the value enters the cyclic data image. The two channels are converted within 400 µs, while the 300 Hz input filter, limit functions and channel status help the controller separate normal process movement from an overloaded or incorrectly wired loop.
Channels 3 and 4 of X67AM1323 convert digital commands into 0–20 mA outputs, pass them through short-circuit protection and connect them to the field through an internal enable relay. The module monitors I/O power separately from the channel values, and its M8 supply path feeds the connected sensors and actuators while enforcing the documented summation-current and voltage-drop limits.
Technical Information
| Brand | B&R |
|---|---|
| Model | X67AM1323 |
| Product Name | X67 Analog Mixed I/O Module |
| System | B&R X67 |
| Analog Inputs | 2 differential current inputs, 0 to 20 mA |
| Input Conversion | 12-bit; 400 µs for both inputs |
| Input Load | <300 Ω |
| Input Filter | 300 Hz cutoff; 40 dB slope |
| Analog Outputs | 2 current outputs, 0 to 20 mA |
| Output Conversion | 12-bit; 400 µs for both outputs |
| Output Settling Time | Approximately 1 ms |
| Maximum Output Load | 400 Ω per channel |
| Output Protection | ±40 mA current limiting; short-circuit proof |
| Output Enable | Internal relay for startup and errors |
| Electrical Isolation | Channels isolated from bus; not isolated channel-to-channel |
| Connections | X2X Link: M12 B-coded; I/O: 4 × M12 A-coded; supply: M8 |
| Supply | 24 VDC nominal; 18 to 30 VDC range |
| Sensor / Actuator Supply | 0.5 A and 12 W maximum |
| Protection and Temperature | IP67; -25 to 60°C operation |
| Dimensions and Weight | 53 × 85 × 42 mm; approximately 175 g |
Current Input Acquisition
The two input channels combine loop wiring, differential measurement and filtering before their values enter the cyclic process image.
Each transmitter current returns through its assigned M12 pair instead of using chassis ground as the measurement conductor. The input load and loop supply must be included in the available voltage calculation.
The A/D converter maps 0–20 mA to the documented integer range. Application scaling turns that integer into engineering units without changing the electrical loop range.
The 300 Hz input filter acts before software evaluation, while configurable limits add channel status alongside the measured value. Neither function can restore a loop with reversed polarity or insufficient supply.
Output Control and Protection
The two output channels generate current commands through independent converters while sharing the module supply and enable conditions.
Each 12-bit command becomes a 0–20 mA output through its D/A path. The receiving load and cable resistance must keep the channel within the 400 Ω load boundary.
The internal relay controls when channels 3 and 4 are connected during startup and error handling. A valid process command therefore does not by itself prove that the field output is enabled.
Short-circuit protection, current limiting and I/O-supply monitoring protect the shared power path. Channel faults and an I/O-supply fault should be diagnosed as separate layers.
Frequently Asked Questions
What should be copied before replacing X67AM1323?+
Why can an X67AM1323 input remain at zero with a powered transmitter?+
How should an X67AM1323 output that cannot reach 20 mA be diagnosed?+
Can X67AM1323 input and output channels share an external return without review?+
Which condition can keep X67AM1323 outputs inactive during startup?+
What information belongs in an X67AM1323 enquiry?+
Obsolete Parts Support
Moore Automation
https://www.mvme.cn/Moore Automation keeps discontinued and current automation references separated by complete manufacturer model. A requested legacy module remains tied to its original suffix, connection scope and quantity so a nearby current product is not recorded as an automatic replacement.






No related record found