Fixed arrangement
2711PC-T10C4D1 has a fixed display and logic configuration.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | Allen-Bradley 2711PC-T10C4D1 PanelView Plus Compact 1000 Terminal |
| Item NO. | 2910410 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | AB |
| Brand | ALLEN-BRADLEY |
| Creation Time | 2026-09-22 |
Allen-Bradley 2711PC-T10C4D1 is a PanelView Plus Compact 1000 operator terminal with a 10.4-inch color TFT display and analog-resistive touch input. It runs FactoryTalk View Machine Edition applications on a fixed display-and-logic configuration.
The 2711PC-T10C4D1 provides one 10/100Base-T Ethernet port, one RS-232 serial port and two USB host ports. A Type 1 CompactFlash slot provides external storage access, while the application flash capacity for the 1000 terminal is 25 MB.
Unlike modular PanelView Plus arrangements, the 2711PC-T10C4D1 does not support communication modules and its logic module is not designed for replacement. The terminal uses a non-isolated 24 V DC input and mounts through a 224 × 305 mm panel opening.
| Technical Item | 2711PC-T10C4D1 |
|---|---|
| Brand | Allen-Bradley |
| Product Type | PanelView Plus Compact 1000 touch terminal |
| Brand Country | United States |
| Display | 10.4 in. color TFT |
| Resolution | 640 × 480 |
| Touch Input | Analog resistive |
| Application Runtime | FactoryTalk View Machine Edition |
| Ethernet | 1 × 10/100Base-T |
| Serial | 1 × RS-232 |
| USB | 2 host ports |
| External Storage | Type 1 CompactFlash |
| Application Flash | 25 MB |
| DC Input | 24 V nominal; 18…32 V DC, non-isolated |
| Panel Cutout | 224 × 305 mm |
2711PC-T10C4D1 has a fixed display and logic configuration.
The Compact terminal does not accept the communication modules used by modular PanelView Plus configurations.
The logic module is not designed as a field-replaceable subassembly.
Installation of 2711PC-T10C4D1 is defined by its cutout, internal clearance and non-isolated supply requirements.
The required cutout is 224 × 305 mm.
Minimum clearances are 51 mm top and bottom, 25 mm at the sides and back, with 102 mm on the card-access side.
The input accepts 18…32 V DC and the rear earth terminal connects to the prescribed low-impedance earth path.
It uses a 10.4-inch color TFT display with 640 × 480 resolution and analog-resistive touch input.
The terminal includes one 10/100Base-T Ethernet port, one RS-232 port and two USB host ports. A Type 1 CompactFlash slot provides removable storage access.
No. The PanelView Plus Compact platform uses a fixed communication configuration and does not support add-on communication modules.
The nominal input is 24 V DC with an accepted range of 18…32 V DC. The input is non-isolated, so the grounding and source arrangement must follow the installation requirements.
The PanelView Plus Compact 1000 touch terminal uses a 224 × 305 mm opening. Allow the documented clearances for ventilation, wiring and CompactFlash access.
No. The Compact configuration is fixed and the logic module is not designed for replacement.
Legacy automation enquiries are handled with the complete catalog number and installed configuration kept visible throughout the quotation.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found