PM865K02 · 3BSE031150R1
PM865 = processor type.
K02 = redundant processor-unit package.
3BSE031150R1 = complete ABB article number; no segment-level meaning is assigned here.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | ABB PM865K02 3BSE031150R1 / PM866AK02 3BSE081637R1 Redundant Processor Units |
| Item NO. | 2931610 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | ABB |
| Brand | ABB |
| Creation Time | 2026-11-10 |
ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1 are redundant processor-unit packages in the AC 800M controller family. Each K02 record supplies a paired CPU arrangement in which one processor runs as primary and the second remains synchronized as hot standby.
The PM865 package belongs to the High Integrity controller class. ABB PM865K02 3BSE031150R1 combines two PM865K01 units with the TK850 CEX-Bus expansion cable and TK851 RCU Link cable. ABB PM866AK02 3BSE081637R1 combines two PM866AK01 processor-unit packages and uses the PM866A platform, whose 64 MB memory and application flash storage differ from the PM865 resources.
Both ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1 accept 24 V DC supply, connect through two Ethernet channels and support a maximum 10 ms processor changeover. Their identical 119 × 186 × 135 mm controller envelope does not make the two order records interchangeable: the complete model and article number must remain together through selection, receiving and configuration.
| Specification |
|
|
|---|---|---|
| Brand | ABB | ABB |
| Model | PM865K02 3BSE031150R1 | PM866AK02 3BSE081637R1 |
| Product Name | Redundant Processor Unit | Redundant Processor Unit |
| Country | Not specified | Not specified |
| Controller family | AC 800M High Integrity | AC 800M |
| Package basis | 2 × PM865K01 processor units | 2 × PM866AK01 processor units |
| High Integrity controller | Yes | No |
| Clock frequency | 96 MHz | 133 MHz |
| Memory | 32 MB | 64 MB |
| RAM available for application | 22.184 MB | 51.389 MB |
| Processor type | MPC862P | MPC866 |
| Flash storage for application data | No | Yes |
| 1000 Boolean operations | 0.17 ms | 0.09 ms |
| Power supply | 24 V DC (19.2–30 V DC) | 24 V DC (19.2–30 V DC) |
| Power consumption, typical / maximum | 287 / 487 mA | 210 / 360 mA |
| Power dissipation, typical | 6.9 W | 5.1 W |
| Redundant switchover | Maximum 10 ms | Maximum 10 ms |
| Ethernet | 2 × 10 Mbit/s RJ-45 | 2 × 10 Mbit/s RJ-45 |
| Operating temperature | +5 to +55 °C | 0 to +55 °C |
| Dimensions, W × H × D | 119 × 186 × 135 mm | 119 × 186 × 135 mm |
| Protection class | IP20 | IP20 |
PM865 = processor type.
K02 = redundant processor-unit package.
3BSE031150R1 = complete ABB article number; no segment-level meaning is assigned here.
PM866A = processor type.
K02 = redundant processor-unit package.
3BSE081637R1 = complete ABB article number; no segment-level meaning is assigned here.
ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1 use the same primary/backup topology, while the processor resources and High Integrity classification remain model-specific.
One processor controls the process and the second tracks the primary as hot standby. Following a changeover, the controller operates with one active processor until the redundant pair is restored.
The TK850 cable extends the CEX-Bus across the two processor sides. The TK851 RCU Link carries status and control information between the CPUs and defines the upper processor identity through its marked connector.
Both processors connect to CN1, or to CN1 and CN2 for redundant Control Network paths. In redundant CPU operation, S800 I/O uses the optical ModuleBus rather than the electrical ModuleBus on TP830.
The two K02 packages expose their operating state through processor indicators, controller logs, power supervision and the condition of the RCU Link.
If DUAL is off on both processors, first allow restart or configuration to finish. Then verify the RCU Link and confirm that both CPUs run the same control software.
A backup-unit fault does not control the primary processor. A primary hardware fault initiates the changeover; the controller log and Fault indicator provide the next diagnostic reference.
Both CPUs receive their own L+ and L− power connections. SA and SB accept redundant power-supply status signals, allowing the controller to distinguish the condition of the two monitored supply paths.
ABB PM865K02 3BSE031150R1 contains two PM865K01 processor units, while ABB PM866AK02 3BSE081637R1 contains two PM866AK01 processor-unit packages. In both cases, the K02 suffix and complete ABB article number identify the paired package; neither record should be shortened to the single-CPU K01 identity.
Allow restart or configuration work to finish, then check the TK851 RCU Link, TK850 CEX-Bus extension path and power to both processors. For ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1, both CPUs must also use compatible control software before the redundant pair can synchronize.
COM3 on TP830 is unavailable in the redundant CPU arrangement; use COM4 on the primary processor when a direct serial service connection is required. ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1 connect S800 I/O through the optical ModuleBus rather than the electrical ModuleBus.
Preserve the exact controller application, control-software level, network arrangement and full order record. After replacement, ABB PM865K02 3BSE031150R1 or ABB PM866AK02 3BSE081637R1 can restore redundancy only when the two processors synchronize correctly through the RCU Link.
Both ABB PM865K02 3BSE031150R1 and ABB PM866AK02 3BSE081637R1 specify a maximum 10 ms processor changeover. Process outputs are frozen during transfer, and the controller then continues on the former standby processor until the redundant pair is restored.
Choose ABB PM865K02 3BSE031150R1 when the High Integrity PM865 controller identity is required. Choose ABB PM866AK02 3BSE081637R1 for the PM866A platform with 64 MB memory, faster Boolean execution and application flash storage; do not treat the common enclosure and redundancy behavior as evidence that the two order records are interchangeable.
Moore Automation coordinates industrial automation enquiries around complete model strings, article numbers and requested quantities. The team can align the submitted record with available documentation and prepare the details required for quotation review.
Once an order is arranged, communication can cover packing information, selected carrier details and shipment tracking updates without changing the manufacturer identity recorded for the requested item.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found