ABB PM5670-2ETH-XC 1SAP351000R0378 Processor Module
Product Introduction
ABB PM5670-2ETH-XC 1SAP351000R0378 is an AC500-XC V3 processor module built around a 1 GHz TI ARM Cortex-A9 32-bit RISC processor. It executes cyclic and time-controlled control tasks while its display and eight function keys provide local access to operating state, diagnosis and settings.
Within ABB PM5670-2ETH-XC 1SAP351000R0378, 160 MB of total user program memory includes 32 MB for program code and data and up to 128 MB for web-server data. Two independent Ethernet interfaces, configurable RS232/RS485 communication and an integrated CAN interface connect the controller to separate network and field-device paths without turning those paths into one shared configuration.
Order code R0378 identifies the R03xx revision of ABB PM5670-2ETH-XC 1SAP351000R0378. This revision requires Automation Builder 2.6.0 or later and firmware 3.6.0 or later, cannot be downgraded below those baselines and is installed only with the dedicated TB56xx-2ETH-XC terminal-base family.
Technical Information
| Brand | ABB |
|---|---|
| Model | PM5670-2ETH-XC 1SAP351000R0378 |
| Product Name | AC500-XC V3 Processor Module |
| Country | Not specified |
| Processor | TI ARM Cortex-A9, 32-bit RISC |
| Processor Clock | 1 GHz |
| Total User Program Memory | 160 MB |
| Maximum Downloadable Application | 176 MB |
| User Program Code and Data | 32 MB |
| User Web Server Data | 128 MB |
| Ethernet Interfaces | 2 independent RJ45 |
| Serial Interface | 1 × RS232 / RS485 |
| CAN Interface | 1 integrated |
| Supply Voltage | 24 V DC |
| Net Weight | 0.137 kg |
Communication and Connectivity
ABB PM5670-2ETH-XC 1SAP351000R0378 separates Ethernet, serial and CAN traffic into distinct interfaces, so every connected network or device needs a defined protocol, address and physical layer.
Dual Ethernet
Two independent RJ45 interfaces carry separate MAC addresses and can also be configured as a two-port switch for one interface.
Ethernet services include programming access, Modbus TCP, web-server functions, IEC 60870-5-104 and OPC UA. Licensed protocols require the applicable runtime license.
Configurable COM1
The internal serial channel changes between RS232 and RS485 and supports documented ASCII or Modbus RTU master/slave roles.
RS485 installations require a consistent bus topology, polarity, termination, baud rate and framing; RS232 uses a point-to-point electrical path.
Integrated CAN
The CAN path supports CANopen Master, CAN 2A/2B, J1939 and CAN synchronization functions through the terminal base.
CAN operation depends on a common bitrate, unique node addresses, suitable cable impedance and termination at the physical ends of the trunk.
Configuration and Programming
The R03xx hardware baseline of ABB PM5670-2ETH-XC 1SAP351000R0378 links the engineering version, memory plan and terminal-base layout to one exact project record.
Establish the R03xx baseline
Open and validate the project with Automation Builder 2.6.0 or later. Match firmware 3.6.0 or later and preserve an untouched project backup before conversion or download.
Size the application deliberately
The maximum downloadable application is 176 MB. Monitor the separate code-and-data and web-data allocations rather than treating the 160 MB CPU class as one unrestricted pool.
Build the terminal-base tree
Select the TB56xx-2ETH-XC base that provides the required communication-module slots, then reproduce each installed module and interface role in the hardware configuration.
Frequently Asked Questions
01Can ABB PM5670-2ETH-XC 1SAP351000R0378 replace the earlier R0278 revision?+
ABB PM5670-2ETH-XC 1SAP351000R0378 is the R03xx successor to the R02xx R0278 revision. The replacement keeps the PM5670-2ETH-XC function class, but the project must be checked against the R03xx engineering and firmware baseline before download.
02Why can an existing project refuse to download to ABB PM5670-2ETH-XC 1SAP351000R0378?+
ABB PM5670-2ETH-XC 1SAP351000R0378 requires Automation Builder 2.6.0 or later and firmware 3.6.0 or later. Confirm the exact R0378 hardware entry, supported libraries, project conversion and terminal-base configuration before retrying the download.
03Why does one Ethernet path on ABB PM5670-2ETH-XC 1SAP351000R0378 remain offline?+
ABB PM5670-2ETH-XC 1SAP351000R0378 has two independent Ethernet interfaces with separate configuration roles. Check the selected interface, MAC and IP settings, protocol assignment, physical link and whether the project intentionally combines the ports as a switch.
04What should be checked when serial communication fails on ABB PM5670-2ETH-XC 1SAP351000R0378?+
For ABB PM5670-2ETH-XC 1SAP351000R0378, confirm whether COM1 is configured for RS232 or RS485, then compare pinout, termination, baud rate, parity and Modbus RTU or ASCII role with the connected device.
05What causes CAN communication errors on ABB PM5670-2ETH-XC 1SAP351000R0378?+
ABB PM5670-2ETH-XC 1SAP351000R0378 depends on matching CAN bitrate, node addressing, cable topology and end termination. Also verify that the project selects the intended CANopen, CAN 2A/2B, J1939 or CAN sync function.
06Which terminal base should be selected for ABB PM5670-2ETH-XC 1SAP351000R0378?+
ABB PM5670-2ETH-XC 1SAP351000R0378 uses the dedicated TB56xx-2ETH-XC family. Select TB5600, TB5610, TB5620, TB5640 or TB5660 according to the required zero, one, two, four or six communication-module slots and reproduce the same arrangement in the hardware tree.
Customer Support
Moore Automation
https://www.mvme.cn/Customer support begins with a complete enquiry record: manufacturer, full model, order code, quantity and destination are kept together before a commercial response is prepared. For ABB PM5670-2ETH-XC 1SAP351000R0378, the R0378 revision, software baseline and terminal-base requirement can remain visible throughout the discussion.





No related record found