CEX-bus exchange
The interface receives controller requests on CEX and returns the collected Satt I/O values through the same expansion-bus path.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | ABB CI865K01 3BSE040795R1 AC 800M Satt I/O Communication Interface Kit |
| Item NO. | 2928398 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | ABB |
| Brand | ABB |
| Creation Time | 2026-10-30 |
ABB CI865K01 3BSE040795R1 is an AC 800M CEX-bus communication interface kit for connecting Satt Rack I/O and Series 200 I/O through the documented ControlNet-based field path. It places legacy Satt I/O data on the controller expansion bus without turning the module into a general-purpose ControlNet adapter.
Within ABB CI865K01 3BSE040795R1, the CEX interface, processor, FPGA and ControlNet ASIC separate controller-bus traffic from the two BNC network channels. The interface can organize up to thirty-one documented nodes and transfers binary or analog process values between those nodes and the AC 800M controller.
Installation of ABB CI865K01 3BSE040795R1 checks the CEX position, TP865 base connection, BNC cabling, network termination and Satt node addresses before power is restored. Hot replacement preserves the documented cabinet and network procedure; it does not remove the need to validate every reconnected node.
| Brand | ABB |
|---|---|
| Model | CI865K01 3BSE040795R1 |
| Product Name | Satt I/O Communication Interface Kit |
| Country | Switzerland |
| System Family | AC 800M / Satt I/O |
| Controller Connection | CEX bus |
| Field Network | ControlNet-based Satt I/O path |
| Field Connectors | Two BNC channels on TP865 |
| Supported I/O | Satt Rack I/O and Series 200 I/O |
| Node Capacity | Up to 31 nodes |
| Binary I/O Capacity | Up to 3968 binary I/O points |
| CEX Current | 120 mA typical; 200 mA maximum at 24 V |
| Power Dissipation | Approx. 2.9 W |
| Protection Rating | IP20 |
| Dimensions / Weight | 59 × 185 × 127.5 mm; approx. 700 g |
The interface receives controller requests on CEX and returns the collected Satt I/O values through the same expansion-bus path.
The TP865 exposes the two field-network channels used by the Satt I/O segment; cable and termination checks follow that network layout.
Each connected Satt node retains its documented address so channel data is mapped to the intended controller object rather than inferred from physical order.
Reserve the documented CEX slot, fit the TP865 base and terminate the expansion bus at the physical endpoint with power removed.
Land the BNC channels and verify cable continuity, segment termination and every Rack I/O or Series 200 node address.
Confirm CI865 recognition in AC 800M, then read and drive representative points at each Satt node before returning the segment to service.
Moore Automation can record discontinued or difficult-to-source industrial part numbers with photographs, revisions and destination requirements.
Any availability statement is confirmed for the individual enquiry; older Satt I/O references are not presented as guaranteed stock or automatic substitutes.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found