CEX-side data path
The CEX interface exchanges mapped block data with the AC 800M controller while the local processor manages the field-network schedule.
Welcome to Moore Automation Limited
Copy and share this link on social network or send it to your friends
Copy| Product Name | ABB CI862 3BUA000037R1 AC 800M TRIO / Genius Communication Interface Kit |
| Item NO. | 2928401 |
| Weight | 0.1 kg = 0.2205 lb = 3.5274 oz |
| Category | ABB |
| Brand | ABB |
| Creation Time | 2026-10-30 |
ABB CI862 3BUA000037R1 is an AC 800M CEX-bus communication interface for integrating TRIO LAN and Genius I/O blocks with the controller. It transfers block data between the field network and the AC 800M application while retaining the external HHM and network-termination functions required by the installed LAN.
The electronics of ABB CI862 3BUA000037R1 combine a 32 MHz ColdFire processor, SDRAM, flash and the Genius communication processor. One TRIO LAN accepts up to thirty documented blocks, and as many as four LANs can be arranged within the system limits; the controller project maps those block addresses to process data.
At installation, ABB CI862 3BUA000037R1 uses the TP862 baseplate for CEX, TRIO LAN, Genius HHM and RS-422 control connections. The termination switch and field cable are set for the actual network endpoint, and the project is checked against the controller family because CI862 is not used with PM891.
| Brand | ABB |
|---|---|
| Model | CI862 3BUA000037R1 |
| Product Name | TRIO / Genius Communication Interface Kit |
| Country | Switzerland |
| System Family | AC 800M |
| Controller Connection | CEX bus through TP862 |
| Field Network | TRIO LAN / Genius I/O |
| Processor | ColdFire MCF5307, 32 MHz |
| Memory | 8 MB SDRAM; 2 MB flash |
| Blocks per LAN | Up to 30 |
| System LAN Count | Up to 4 within system limits |
| Point Capacity | Up to 1000 points |
| Service Interface | Genius HHM connection |
| CEX Current | 190 mA typical; 200 mA maximum at 24 V |
| Compatibility Boundary | Not supported with PM891 |
The CEX interface exchanges mapped block data with the AC 800M controller while the local processor manages the field-network schedule.
The Genius communication processor drives the TRIO LAN and associates each configured block address with its controller data object.
The baseplate provides the Genius HHM and RS-422 control connections used for documented network setup and service actions.
Record the CEX position, block addresses, cable route and termination state, then isolate cabinet and field-network power before releasing the baseplate wiring.
Connect the documented TRIO/Genius cable, set the termination switch for the actual segment endpoint and preserve the HHM/service connection.
Confirm CI862 recognition, scan every configured block and compare representative input/output values with the field devices before enabling automatic control.
Moore Automation maintains multi-brand automation records across controllers, communication hardware, I/O and monitoring products.
Exact model strings, photographs, quantities and destination details stay connected so a legacy communication interface is reviewed against one consistent enquiry.
Moore Automation Sales Team
Copyright © 2004–2026 www.mvme.cn. All rights reserved.
Disclaimer: Moore Automation Limited is an independent reseller and is not an authorized distributor or representative of the manufacturers featured on this website. Product names and trademarks belong to their respective owners.
No related record found